⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelquerschnitt für 250 Ampere bei 10 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 250 A über 10 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)120 mm²Drop: 0.77V (0.19%)
Aluminum Cable (≤3% Drop)185 mm²Drop: 0.83V (0.21%)
Voltage at Load399.2 VLine Loss: 334.4 W
Max Power & Breaker173.21 kW250A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 250A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A61.78 V (15.44%)338.2 V101.9 V (25.48%)26750.0 WDrop High
2.5 mm²24 A18 A37.07 V (9.27%)362.9 V61.14 V (15.29%)16050.0 WDrop High
4 mm²32 A25 A23.17 V (5.79%)376.8 V38.21 V (9.55%)10031.2 WDrop High
6 mm²41 A32 A15.44 V (3.86%)384.6 V25.48 V (6.37%)6687.5 WDrop High
10 mm²57 A44 A9.27 V (2.32%)390.7 V15.29 V (3.82%)4012.5 WDrop High
16 mm²76 A59 A5.79 V (1.45%)394.2 V9.55 V (2.39%)2507.8 WDrop High
25 mm²101 A78 A3.71 V (0.93%)396.3 V6.11 V (1.53%)1605.0 WDrop High
35 mm²125 A97 A2.65 V (0.66%)397.4 V4.37 V (1.09%)1146.4 WDrop High
50 mm²151 A118 A1.85 V (0.46%)398.1 V3.06 V (0.76%)802.5 WDrop High
70 mm²192 A150 A1.32 V (0.33%)398.7 V2.18 V (0.55%)573.2 WDrop High
95 mm²232 A181 A0.98 V (0.24%)399.0 V1.61 V (0.4%)422.4 WDrop High
120 mm²269 A210 A0.77 V (0.19%)399.2 V1.27 V (0.32%)334.4 W✓ OK (≤3%)
150 mm²309 A241 A0.62 V (0.15%)399.4 V1.02 V (0.25%)267.5 W✓ OK (≤3%)
185 mm²353 A275 A0.5 V (0.13%)399.5 V0.83 V (0.21%)216.9 W✓ OK (≤3%)
240 mm²415 A324 A0.39 V (0.1%)399.6 V0.64 V (0.16%)167.2 W✓ OK (≤3%)
300 mm²477 A372 A0.31 V (0.08%)399.7 V0.51 V (0.13%)133.8 W✓ OK (≤3%)
400 mm²570 A445 A0.23 V (0.06%)399.8 V0.38 V (0.1%)100.3 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 250 Ampere bei 10 Meter (400V)

Welcher Kabelquerschnitt wird für 250A bei 10m (400V) benötigt?

Für 250 Ampere über 10 Meter bei 400V wird ein Kupferkabel von 120 mm² empfohlen, um den Spannungsfall unter 3% (0.77V bzw. 0.19%) zu halten.

Wie hoch ist die maximale Leistung bei 250A und 400V?

Die übertragbare Leistung beträgt 173.21 kW bei einer empfohlenen Absicherung von 250A.