Kabelquerschnitt für 275 Ampere bei 350 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 275 A über 350 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)300 mm²Drop: 11.89V (2.97%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 14.71V (3.68%)
Voltage at Load388.1 VLine Loss: 5664.3 W
Max Power & Breaker190.53 kW300A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 275A at 350m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2378.39 V (594.6%)0.0 V3923.24 V (980.81%)1132862.5 WDrop High
2.5 mm²24 A18 A1427.04 V (356.76%)0.0 V2353.94 V (588.49%)679717.5 WDrop High
4 mm²32 A25 A891.9 V (222.97%)0.0 V1471.21 V (367.8%)424823.4 WDrop High
6 mm²41 A32 A594.6 V (148.65%)0.0 V980.81 V (245.2%)283215.6 WDrop High
10 mm²57 A44 A356.76 V (89.19%)43.2 V588.49 V (147.12%)169929.4 WDrop High
16 mm²76 A59 A222.97 V (55.74%)177.0 V367.8 V (91.95%)106205.9 WDrop High
25 mm²101 A78 A142.7 V (35.68%)257.3 V235.39 V (58.85%)67971.8 WDrop High
35 mm²125 A97 A101.93 V (25.48%)298.1 V168.14 V (42.03%)48551.2 WDrop High
50 mm²151 A118 A71.35 V (17.84%)328.6 V117.7 V (29.42%)33985.9 WDrop High
70 mm²192 A150 A50.97 V (12.74%)349.0 V84.07 V (21.02%)24275.6 WDrop High
95 mm²232 A181 A37.55 V (9.39%)362.4 V61.95 V (15.49%)17887.3 WDrop High
120 mm²269 A210 A29.73 V (7.43%)370.3 V49.04 V (12.26%)14160.8 WDrop High
150 mm²309 A241 A23.78 V (5.95%)376.2 V39.23 V (9.81%)11328.6 WDrop High
185 mm²353 A275 A19.28 V (4.82%)380.7 V31.81 V (7.95%)9185.4 W~ ≤5%
240 mm²415 A324 A14.86 V (3.72%)385.1 V24.52 V (6.13%)7080.4 W~ ≤5%
300 mm²477 A372 A11.89 V (2.97%)388.1 V19.62 V (4.9%)5664.3 W✓ OK (≤3%)
400 mm²570 A445 A8.92 V (2.23%)391.1 V14.71 V (3.68%)4248.2 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 275 Ampere bei 350 Meter (400V)

Welcher Kabelquerschnitt wird für 275A bei 350m (400V) benötigt?

Für 275 Ampere über 350 Meter bei 400V wird ein Kupferkabel von 300 mm² empfohlen, um den Spannungsfall unter 3% (11.89V bzw. 2.97%) zu halten.

Wie hoch ist die maximale Leistung bei 275A und 400V?

Die übertragbare Leistung beträgt 190.53 kW bei einer empfohlenen Absicherung von 300A.