Kabelquerschnitt für 125 Ampere bei 350 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 125 A über 350 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)150 mm²Drop: 10.81V (2.7%)
Aluminum Cable (≤3% Drop)240 mm²Drop: 11.15V (2.79%)
Voltage at Load389.2 VLine Loss: 2340.6 W
Max Power & Breaker86.6 kW125A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 350m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1081.09 V (270.27%)0.0 V1783.29 V (445.82%)234062.5 WDrop High
2.5 mm²24 A18 A648.65 V (162.16%)0.0 V1069.97 V (267.49%)140437.5 WDrop High
4 mm²32 A25 A405.41 V (101.35%)0.0 V668.73 V (167.18%)87773.4 WDrop High
6 mm²41 A32 A270.27 V (67.57%)129.7 V445.82 V (111.46%)58515.6 WDrop High
10 mm²57 A44 A162.16 V (40.54%)237.8 V267.49 V (66.87%)35109.4 WDrop High
16 mm²76 A59 A101.35 V (25.34%)298.6 V167.18 V (41.8%)21943.4 WDrop High
25 mm²101 A78 A64.87 V (16.22%)335.1 V107.0 V (26.75%)14043.7 WDrop High
35 mm²125 A97 A46.33 V (11.58%)353.7 V76.43 V (19.11%)10031.2 WDrop High
50 mm²151 A118 A32.43 V (8.11%)367.6 V53.5 V (13.37%)7021.9 WDrop High
70 mm²192 A150 A23.17 V (5.79%)376.8 V38.21 V (9.55%)5015.6 WDrop High
95 mm²232 A181 A17.07 V (4.27%)382.9 V28.16 V (7.04%)3695.7 W~ ≤5%
120 mm²269 A210 A13.51 V (3.38%)386.5 V22.29 V (5.57%)2925.8 W~ ≤5%
150 mm²309 A241 A10.81 V (2.7%)389.2 V17.83 V (4.46%)2340.6 W✓ OK (≤3%)
185 mm²353 A275 A8.77 V (2.19%)391.2 V14.46 V (3.61%)1897.8 W✓ OK (≤3%)
240 mm²415 A324 A6.76 V (1.69%)393.2 V11.15 V (2.79%)1462.9 W✓ OK (≤3%)
300 mm²477 A372 A5.41 V (1.35%)394.6 V8.92 V (2.23%)1170.3 W✓ OK (≤3%)
400 mm²570 A445 A4.05 V (1.01%)395.9 V6.69 V (1.67%)877.7 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 125 Ampere bei 350 Meter (400V)

Welcher Kabelquerschnitt wird für 125A bei 350m (400V) benötigt?

Für 125 Ampere über 350 Meter bei 400V wird ein Kupferkabel von 150 mm² empfohlen, um den Spannungsfall unter 3% (10.81V bzw. 2.7%) zu halten.

Wie hoch ist die maximale Leistung bei 125A und 400V?

Die übertragbare Leistung beträgt 86.6 kW bei einer empfohlenen Absicherung von 125A.