Kabelquerschnitt für 300 Ampere bei 175 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 300 A über 175 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)185 mm²Drop: 10.52V (2.63%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 10.7V (2.67%)
Voltage at Load389.5 VLine Loss: 5465.7 W
Max Power & Breaker207.85 kW300A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 300A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1297.31 V (324.33%)0.0 V2139.95 V (534.99%)674100.0 WDrop High
2.5 mm²24 A18 A778.38 V (194.6%)0.0 V1283.97 V (320.99%)404460.0 WDrop High
4 mm²32 A25 A486.49 V (121.62%)0.0 V802.48 V (200.62%)252787.5 WDrop High
6 mm²41 A32 A324.33 V (81.08%)75.7 V534.99 V (133.75%)168525.0 WDrop High
10 mm²57 A44 A194.6 V (48.65%)205.4 V320.99 V (80.25%)101115.0 WDrop High
16 mm²76 A59 A121.62 V (30.41%)278.4 V200.62 V (50.16%)63196.9 WDrop High
25 mm²101 A78 A77.84 V (19.46%)322.2 V128.4 V (32.1%)40446.0 WDrop High
35 mm²125 A97 A55.6 V (13.9%)344.4 V91.71 V (22.93%)28890.0 WDrop High
50 mm²151 A118 A38.92 V (9.73%)361.1 V64.2 V (16.05%)20223.0 WDrop High
70 mm²192 A150 A27.8 V (6.95%)372.2 V45.86 V (11.46%)14445.0 WDrop High
95 mm²232 A181 A20.48 V (5.12%)379.5 V33.79 V (8.45%)10643.7 WDrop High
120 mm²269 A210 A16.22 V (4.05%)383.8 V26.75 V (6.69%)8426.2 WDrop High
150 mm²309 A241 A12.97 V (3.24%)387.0 V21.4 V (5.35%)6741.0 W~ ≤5%
185 mm²353 A275 A10.52 V (2.63%)389.5 V17.35 V (4.34%)5465.7 W✓ OK (≤3%)
240 mm²415 A324 A8.11 V (2.03%)391.9 V13.37 V (3.34%)4213.1 W✓ OK (≤3%)
300 mm²477 A372 A6.49 V (1.62%)393.5 V10.7 V (2.67%)3370.5 W✓ OK (≤3%)
400 mm²570 A445 A4.86 V (1.22%)395.1 V8.02 V (2.01%)2527.9 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 300 Ampere bei 175 Meter (400V)

Welcher Kabelquerschnitt wird für 300A bei 175m (400V) benötigt?

Für 300 Ampere über 175 Meter bei 400V wird ein Kupferkabel von 185 mm² empfohlen, um den Spannungsfall unter 3% (10.52V bzw. 2.63%) zu halten.

Wie hoch ist die maximale Leistung bei 300A und 400V?

Die übertragbare Leistung beträgt 207.85 kW bei einer empfohlenen Absicherung von 300A.