Kabelquerschnitt für 300 Ampere bei 200 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 300 A über 200 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)240 mm²Drop: 9.27V (2.32%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 9.17V (2.29%)
Voltage at Load390.7 VLine Loss: 4815.0 W
Max Power & Breaker207.85 kW300A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 300A at 200m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1482.64 V (370.66%)0.0 V2445.66 V (611.41%)770400.0 WDrop High
2.5 mm²24 A18 A889.58 V (222.4%)0.0 V1467.39 V (366.85%)462240.0 WDrop High
4 mm²32 A25 A555.99 V (139.0%)0.0 V917.12 V (229.28%)288900.0 WDrop High
6 mm²41 A32 A370.66 V (92.66%)29.3 V611.41 V (152.85%)192600.0 WDrop High
10 mm²57 A44 A222.4 V (55.6%)177.6 V366.85 V (91.71%)115560.0 WDrop High
16 mm²76 A59 A139.0 V (34.75%)261.0 V229.28 V (57.32%)72225.0 WDrop High
25 mm²101 A78 A88.96 V (22.24%)311.0 V146.74 V (36.68%)46224.0 WDrop High
35 mm²125 A97 A63.54 V (15.89%)336.5 V104.81 V (26.2%)33017.1 WDrop High
50 mm²151 A118 A44.48 V (11.12%)355.5 V73.37 V (18.34%)23112.0 WDrop High
70 mm²192 A150 A31.77 V (7.94%)368.2 V52.41 V (13.1%)16508.6 WDrop High
95 mm²232 A181 A23.41 V (5.85%)376.6 V38.62 V (9.65%)12164.2 WDrop High
120 mm²269 A210 A18.53 V (4.63%)381.5 V30.57 V (7.64%)9630.0 WDrop High
150 mm²309 A241 A14.83 V (3.71%)385.2 V24.46 V (6.11%)7704.0 W~ ≤5%
185 mm²353 A275 A12.02 V (3.01%)388.0 V19.83 V (4.96%)6246.5 W~ ≤5%
240 mm²415 A324 A9.27 V (2.32%)390.7 V15.29 V (3.82%)4815.0 W✓ OK (≤3%)
300 mm²477 A372 A7.41 V (1.85%)392.6 V12.23 V (3.06%)3852.0 W✓ OK (≤3%)
400 mm²570 A445 A5.56 V (1.39%)394.4 V9.17 V (2.29%)2889.0 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 300 Ampere bei 200 Meter (400V)

Welcher Kabelquerschnitt wird für 300A bei 200m (400V) benötigt?

Für 300 Ampere über 200 Meter bei 400V wird ein Kupferkabel von 240 mm² empfohlen, um den Spannungsfall unter 3% (9.27V bzw. 2.32%) zu halten.

Wie hoch ist die maximale Leistung bei 300A und 400V?

Die übertragbare Leistung beträgt 207.85 kW bei einer empfohlenen Absicherung von 300A.