⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelquerschnitt für 32 Ampere bei 90 Meter (230V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 32 A über 90 m einfache Leitungslänge bei 230V.

Copper Cable (≤3% Drop)25 mm²Drop: 4.93V (2.14%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 5.81V (2.53%)
Voltage at Load225.1 VLine Loss: 157.8 W
Max Power & Breaker7.36 kW32A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 90m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A82.18 V (35.73%)147.8 V135.55 V (58.94%)2629.6 WDrop High
2.5 mm²24 A18 A49.31 V (21.44%)180.7 V81.33 V (35.36%)1577.8 WDrop High
4 mm²32 A25 A30.82 V (13.4%)199.2 V50.83 V (22.1%)986.1 WDrop High
6 mm²41 A32 A20.54 V (8.93%)209.5 V33.89 V (14.73%)657.4 WDrop High
10 mm²57 A44 A12.33 V (5.36%)217.7 V20.33 V (8.84%)394.4 WDrop High
16 mm²76 A59 A7.7 V (3.35%)222.3 V12.71 V (5.53%)246.5 W~ ≤5%
25 mm²101 A78 A4.93 V (2.14%)225.1 V8.13 V (3.54%)157.8 W✓ OK (≤3%)
35 mm²125 A97 A3.52 V (1.53%)226.5 V5.81 V (2.53%)112.7 W✓ OK (≤3%)
50 mm²151 A118 A2.47 V (1.07%)227.5 V4.07 V (1.77%)78.9 W✓ OK (≤3%)
70 mm²192 A150 A1.76 V (0.77%)228.2 V2.9 V (1.26%)56.3 W✓ OK (≤3%)
95 mm²232 A181 A1.3 V (0.56%)228.7 V2.14 V (0.93%)41.5 W✓ OK (≤3%)
120 mm²269 A210 A1.03 V (0.45%)229.0 V1.69 V (0.74%)32.9 W✓ OK (≤3%)
150 mm²309 A241 A0.82 V (0.36%)229.2 V1.36 V (0.59%)26.3 W✓ OK (≤3%)
185 mm²353 A275 A0.67 V (0.29%)229.3 V1.1 V (0.48%)21.3 W✓ OK (≤3%)
240 mm²415 A324 A0.51 V (0.22%)229.5 V0.85 V (0.37%)16.4 W✓ OK (≤3%)
300 mm²477 A372 A0.41 V (0.18%)229.6 V0.68 V (0.29%)13.1 W✓ OK (≤3%)
400 mm²570 A445 A0.31 V (0.13%)229.7 V0.51 V (0.22%)9.9 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 32 Ampere bei 90 Meter (230V)

Welcher Kabelquerschnitt wird für 32A bei 90m (230V) benötigt?

Für 32 Ampere über 90 Meter bei 230V wird ein Kupferkabel von 25 mm² empfohlen, um den Spannungsfall unter 3% (4.93V bzw. 2.14%) zu halten.

Wie hoch ist die maximale Leistung bei 32A und 230V?

Die übertragbare Leistung beträgt 7.36 kW bei einer empfohlenen Absicherung von 32A.