Kabelquerschnitt für 325 Ampere bei 150 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 325 A über 150 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)185 mm²Drop: 9.77V (2.44%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 9.94V (2.48%)
Voltage at Load390.2 VLine Loss: 5498.2 W
Max Power & Breaker225.17 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 150m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1204.64 V (301.16%)0.0 V1987.1 V (496.77%)678112.5 WDrop High
2.5 mm²24 A18 A722.78 V (180.7%)0.0 V1192.26 V (298.06%)406867.5 WDrop High
4 mm²32 A25 A451.74 V (112.94%)0.0 V745.16 V (186.29%)254292.2 WDrop High
6 mm²41 A32 A301.16 V (75.29%)98.8 V496.77 V (124.19%)169528.1 WDrop High
10 mm²57 A44 A180.7 V (45.17%)219.3 V298.06 V (74.52%)101716.9 WDrop High
16 mm²76 A59 A112.94 V (28.23%)287.1 V186.29 V (46.57%)63573.0 WDrop High
25 mm²101 A78 A72.28 V (18.07%)327.7 V119.23 V (29.81%)40686.7 WDrop High
35 mm²125 A97 A51.63 V (12.91%)348.4 V85.16 V (21.29%)29062.0 WDrop High
50 mm²151 A118 A36.14 V (9.03%)363.9 V59.61 V (14.9%)20343.4 WDrop High
70 mm²192 A150 A25.81 V (6.45%)374.2 V42.58 V (10.65%)14531.0 WDrop High
95 mm²232 A181 A19.02 V (4.76%)381.0 V31.38 V (7.84%)10707.0 WDrop High
120 mm²269 A210 A15.06 V (3.76%)384.9 V24.84 V (6.21%)8476.4 WDrop High
150 mm²309 A241 A12.05 V (3.01%)388.0 V19.87 V (4.97%)6781.1 WDrop High
185 mm²353 A275 A9.77 V (2.44%)390.2 V16.11 V (4.03%)5498.2 W✓ OK (≤3%)
240 mm²415 A324 A7.53 V (1.88%)392.5 V12.42 V (3.1%)4238.2 W✓ OK (≤3%)
300 mm²477 A372 A6.02 V (1.51%)394.0 V9.94 V (2.48%)3390.6 W✓ OK (≤3%)
400 mm²570 A445 A4.52 V (1.13%)395.5 V7.45 V (1.86%)2542.9 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 325 Ampere bei 150 Meter (400V)

Welcher Kabelquerschnitt wird für 325A bei 150m (400V) benötigt?

Für 325 Ampere über 150 Meter bei 400V wird ein Kupferkabel von 185 mm² empfohlen, um den Spannungsfall unter 3% (9.77V bzw. 2.44%) zu halten.

Wie hoch ist die maximale Leistung bei 325A und 400V?

Die übertragbare Leistung beträgt 225.17 kW bei einer empfohlenen Absicherung von 350A.