Kabelquerschnitt für 35 Ampere bei 10 Meter (230V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 35 A über 10 m einfache Leitungslänge bei 230V.

Copper Cable (≤3% Drop)6 mm²Drop: 2.5V (1.09%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 2.47V (1.07%)
Voltage at Load227.5 VLine Loss: 87.4 W
Max Power & Breaker8.05 kW35A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 35A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A9.99 V (4.34%)220.0 V16.47 V (7.16%)349.5 WDrop High
2.5 mm²24 A18 A5.99 V (2.61%)224.0 V9.88 V (4.3%)209.7 WDrop High
4 mm²32 A25 A3.75 V (1.63%)226.3 V6.18 V (2.69%)131.1 WDrop High
6 mm²41 A32 A2.5 V (1.09%)227.5 V4.12 V (1.79%)87.4 W✓ OK (≤3%)
10 mm²57 A44 A1.5 V (0.65%)228.5 V2.47 V (1.07%)52.4 W✓ OK (≤3%)
16 mm²76 A59 A0.94 V (0.41%)229.1 V1.54 V (0.67%)32.8 W✓ OK (≤3%)
25 mm²101 A78 A0.6 V (0.26%)229.4 V0.99 V (0.43%)21.0 W✓ OK (≤3%)
35 mm²125 A97 A0.43 V (0.19%)229.6 V0.71 V (0.31%)15.0 W✓ OK (≤3%)
50 mm²151 A118 A0.3 V (0.13%)229.7 V0.49 V (0.21%)10.5 W✓ OK (≤3%)
70 mm²192 A150 A0.21 V (0.09%)229.8 V0.35 V (0.15%)7.5 W✓ OK (≤3%)
95 mm²232 A181 A0.16 V (0.07%)229.8 V0.26 V (0.11%)5.5 W✓ OK (≤3%)
120 mm²269 A210 A0.12 V (0.05%)229.9 V0.21 V (0.09%)4.4 W✓ OK (≤3%)
150 mm²309 A241 A0.1 V (0.04%)229.9 V0.16 V (0.07%)3.5 W✓ OK (≤3%)
185 mm²353 A275 A0.08 V (0.04%)229.9 V0.13 V (0.06%)2.8 W✓ OK (≤3%)
240 mm²415 A324 A0.06 V (0.03%)229.9 V0.1 V (0.04%)2.2 W✓ OK (≤3%)
300 mm²477 A372 A0.05 V (0.02%)230.0 V0.08 V (0.04%)1.7 W✓ OK (≤3%)
400 mm²570 A445 A0.04 V (0.02%)230.0 V0.06 V (0.03%)1.3 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 35 Ampere bei 10 Meter (230V)

Welcher Kabelquerschnitt wird für 35A bei 10m (230V) benötigt?

Für 35 Ampere über 10 Meter bei 230V wird ein Kupferkabel von 6 mm² empfohlen, um den Spannungsfall unter 3% (2.5V bzw. 1.09%) zu halten.

Wie hoch ist die maximale Leistung bei 35A und 230V?

Die übertragbare Leistung beträgt 8.05 kW bei einer empfohlenen Absicherung von 35A.