Kabelquerschnitt für 35 Ampere bei 40 Meter (230V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 35 A über 40 m einfache Leitungslänge bei 230V.

Copper Cable (≤3% Drop)10 mm²Drop: 5.99V (2.61%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 6.18V (2.69%)
Voltage at Load224.0 VLine Loss: 209.7 W
Max Power & Breaker8.05 kW35A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 35A at 40m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A39.95 V (17.37%)190.1 V65.89 V (28.65%)1398.1 WDrop High
2.5 mm²24 A18 A23.97 V (10.42%)206.0 V39.54 V (17.19%)838.9 WDrop High
4 mm²32 A25 A14.98 V (6.51%)215.0 V24.71 V (10.74%)524.3 WDrop High
6 mm²41 A32 A9.99 V (4.34%)220.0 V16.47 V (7.16%)349.5 W~ ≤5%
10 mm²57 A44 A5.99 V (2.61%)224.0 V9.88 V (4.3%)209.7 W✓ OK (≤3%)
16 mm²76 A59 A3.75 V (1.63%)226.3 V6.18 V (2.69%)131.1 W✓ OK (≤3%)
25 mm²101 A78 A2.4 V (1.04%)227.6 V3.95 V (1.72%)83.9 W✓ OK (≤3%)
35 mm²125 A97 A1.71 V (0.74%)228.3 V2.82 V (1.23%)59.9 W✓ OK (≤3%)
50 mm²151 A118 A1.2 V (0.52%)228.8 V1.98 V (0.86%)41.9 W✓ OK (≤3%)
70 mm²192 A150 A0.86 V (0.37%)229.1 V1.41 V (0.61%)30.0 W✓ OK (≤3%)
95 mm²232 A181 A0.63 V (0.27%)229.4 V1.04 V (0.45%)22.1 W✓ OK (≤3%)
120 mm²269 A210 A0.5 V (0.22%)229.5 V0.82 V (0.36%)17.5 W✓ OK (≤3%)
150 mm²309 A241 A0.4 V (0.17%)229.6 V0.66 V (0.29%)14.0 W✓ OK (≤3%)
185 mm²353 A275 A0.32 V (0.14%)229.7 V0.53 V (0.23%)11.3 W✓ OK (≤3%)
240 mm²415 A324 A0.25 V (0.11%)229.8 V0.41 V (0.18%)8.7 W✓ OK (≤3%)
300 mm²477 A372 A0.2 V (0.09%)229.8 V0.33 V (0.14%)7.0 W✓ OK (≤3%)
400 mm²570 A445 A0.15 V (0.07%)229.9 V0.25 V (0.11%)5.2 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 35 Ampere bei 40 Meter (230V)

Welcher Kabelquerschnitt wird für 35A bei 40m (230V) benötigt?

Für 35 Ampere über 40 Meter bei 230V wird ein Kupferkabel von 10 mm² empfohlen, um den Spannungsfall unter 3% (5.99V bzw. 2.61%) zu halten.

Wie hoch ist die maximale Leistung bei 35A und 230V?

Die übertragbare Leistung beträgt 8.05 kW bei einer empfohlenen Absicherung von 35A.