Kabelquerschnitt für 35 Ampere bei 250 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 35 A über 250 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)35 mm²Drop: 9.27V (2.32%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 10.7V (2.67%)
Voltage at Load390.7 VLine Loss: 561.8 W
Max Power & Breaker24.25 kW35A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 35A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A216.22 V (54.05%)183.8 V356.66 V (89.16%)13107.5 WDrop High
2.5 mm²24 A18 A129.73 V (32.43%)270.3 V213.99 V (53.5%)7864.5 WDrop High
4 mm²32 A25 A81.08 V (20.27%)318.9 V133.75 V (33.44%)4915.3 WDrop High
6 mm²41 A32 A54.05 V (13.51%)345.9 V89.16 V (22.29%)3276.9 WDrop High
10 mm²57 A44 A32.43 V (8.11%)367.6 V53.5 V (13.37%)1966.1 WDrop High
16 mm²76 A59 A20.27 V (5.07%)379.7 V33.44 V (8.36%)1228.8 WDrop High
25 mm²101 A78 A12.97 V (3.24%)387.0 V21.4 V (5.35%)786.4 W~ ≤5%
35 mm²125 A97 A9.27 V (2.32%)390.7 V15.29 V (3.82%)561.8 W✓ OK (≤3%)
50 mm²151 A118 A6.49 V (1.62%)393.5 V10.7 V (2.67%)393.2 W✓ OK (≤3%)
70 mm²192 A150 A4.63 V (1.16%)395.4 V7.64 V (1.91%)280.9 W✓ OK (≤3%)
95 mm²232 A181 A3.41 V (0.85%)396.6 V5.63 V (1.41%)207.0 W✓ OK (≤3%)
120 mm²269 A210 A2.7 V (0.68%)397.3 V4.46 V (1.11%)163.8 W✓ OK (≤3%)
150 mm²309 A241 A2.16 V (0.54%)397.8 V3.57 V (0.89%)131.1 W✓ OK (≤3%)
185 mm²353 A275 A1.75 V (0.44%)398.2 V2.89 V (0.72%)106.3 W✓ OK (≤3%)
240 mm²415 A324 A1.35 V (0.34%)398.6 V2.23 V (0.56%)81.9 W✓ OK (≤3%)
300 mm²477 A372 A1.08 V (0.27%)398.9 V1.78 V (0.45%)65.5 W✓ OK (≤3%)
400 mm²570 A445 A0.81 V (0.2%)399.2 V1.34 V (0.33%)49.2 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 35 Ampere bei 250 Meter (400V)

Welcher Kabelquerschnitt wird für 35A bei 250m (400V) benötigt?

Für 35 Ampere über 250 Meter bei 400V wird ein Kupferkabel von 35 mm² empfohlen, um den Spannungsfall unter 3% (9.27V bzw. 2.32%) zu halten.

Wie hoch ist die maximale Leistung bei 35A und 400V?

Die übertragbare Leistung beträgt 24.25 kW bei einer empfohlenen Absicherung von 35A.