Kabelquerschnitt für 350 Ampere bei 250 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 350 A über 250 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)300 mm²Drop: 10.81V (2.7%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 13.37V (3.34%)
Voltage at Load389.2 VLine Loss: 6553.8 W
Max Power & Breaker242.49 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 350A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2162.18 V (540.54%)0.0 V3566.58 V (891.65%)1310750.0 WDrop High
2.5 mm²24 A18 A1297.31 V (324.33%)0.0 V2139.95 V (534.99%)786450.0 WDrop High
4 mm²32 A25 A810.82 V (202.7%)0.0 V1337.47 V (334.37%)491531.2 WDrop High
6 mm²41 A32 A540.54 V (135.14%)0.0 V891.65 V (222.91%)327687.5 WDrop High
10 mm²57 A44 A324.33 V (81.08%)75.7 V534.99 V (133.75%)196612.5 WDrop High
16 mm²76 A59 A202.7 V (50.68%)197.3 V334.37 V (83.59%)122882.8 WDrop High
25 mm²101 A78 A129.73 V (32.43%)270.3 V213.99 V (53.5%)78645.0 WDrop High
35 mm²125 A97 A92.66 V (23.17%)307.3 V152.85 V (38.21%)56175.0 WDrop High
50 mm²151 A118 A64.87 V (16.22%)335.1 V107.0 V (26.75%)39322.5 WDrop High
70 mm²192 A150 A46.33 V (11.58%)353.7 V76.43 V (19.11%)28087.5 WDrop High
95 mm²232 A181 A34.14 V (8.53%)365.9 V56.31 V (14.08%)20696.1 WDrop High
120 mm²269 A210 A27.03 V (6.76%)373.0 V44.58 V (11.15%)16384.4 WDrop High
150 mm²309 A241 A21.62 V (5.41%)378.4 V35.67 V (8.92%)13107.5 WDrop High
185 mm²353 A275 A17.53 V (4.38%)382.5 V28.92 V (7.23%)10627.7 W~ ≤5%
240 mm²415 A324 A13.51 V (3.38%)386.5 V22.29 V (5.57%)8192.2 W~ ≤5%
300 mm²477 A372 A10.81 V (2.7%)389.2 V17.83 V (4.46%)6553.8 W✓ OK (≤3%)
400 mm²570 A445 A8.11 V (2.03%)391.9 V13.37 V (3.34%)4915.3 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 350 Ampere bei 250 Meter (400V)

Welcher Kabelquerschnitt wird für 350A bei 250m (400V) benötigt?

Für 350 Ampere über 250 Meter bei 400V wird ein Kupferkabel von 300 mm² empfohlen, um den Spannungsfall unter 3% (10.81V bzw. 2.7%) zu halten.

Wie hoch ist die maximale Leistung bei 350A und 400V?

Die übertragbare Leistung beträgt 242.49 kW bei einer empfohlenen Absicherung von 350A.