Kabelquerschnitt für 40 Ampere bei 120 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 40 A über 120 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)16 mm²Drop: 11.12V (2.78%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 11.74V (2.93%)
Voltage at Load388.9 VLine Loss: 770.4 W
Max Power & Breaker27.71 kW40A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 40A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A118.61 V (29.65%)281.4 V195.65 V (48.91%)8217.6 WDrop High
2.5 mm²24 A18 A71.17 V (17.79%)328.8 V117.39 V (29.35%)4930.6 WDrop High
4 mm²32 A25 A44.48 V (11.12%)355.5 V73.37 V (18.34%)3081.6 WDrop High
6 mm²41 A32 A29.65 V (7.41%)370.3 V48.91 V (12.23%)2054.4 WDrop High
10 mm²57 A44 A17.79 V (4.45%)382.2 V29.35 V (7.34%)1232.6 W~ ≤5%
16 mm²76 A59 A11.12 V (2.78%)388.9 V18.34 V (4.59%)770.4 W✓ OK (≤3%)
25 mm²101 A78 A7.12 V (1.78%)392.9 V11.74 V (2.93%)493.1 W✓ OK (≤3%)
35 mm²125 A97 A5.08 V (1.27%)394.9 V8.39 V (2.1%)352.2 W✓ OK (≤3%)
50 mm²151 A118 A3.56 V (0.89%)396.4 V5.87 V (1.47%)246.5 W✓ OK (≤3%)
70 mm²192 A150 A2.54 V (0.64%)397.5 V4.19 V (1.05%)176.1 W✓ OK (≤3%)
95 mm²232 A181 A1.87 V (0.47%)398.1 V3.09 V (0.77%)129.8 W✓ OK (≤3%)
120 mm²269 A210 A1.48 V (0.37%)398.5 V2.45 V (0.61%)102.7 W✓ OK (≤3%)
150 mm²309 A241 A1.19 V (0.3%)398.8 V1.96 V (0.49%)82.2 W✓ OK (≤3%)
185 mm²353 A275 A0.96 V (0.24%)399.0 V1.59 V (0.4%)66.6 W✓ OK (≤3%)
240 mm²415 A324 A0.74 V (0.19%)399.3 V1.22 V (0.31%)51.4 W✓ OK (≤3%)
300 mm²477 A372 A0.59 V (0.15%)399.4 V0.98 V (0.24%)41.1 W✓ OK (≤3%)
400 mm²570 A445 A0.44 V (0.11%)399.6 V0.73 V (0.18%)30.8 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 40 Ampere bei 120 Meter (400V)

Welcher Kabelquerschnitt wird für 40A bei 120m (400V) benötigt?

Für 40 Ampere über 120 Meter bei 400V wird ein Kupferkabel von 16 mm² empfohlen, um den Spannungsfall unter 3% (11.12V bzw. 2.78%) zu halten.

Wie hoch ist die maximale Leistung bei 40A und 400V?

Die übertragbare Leistung beträgt 27.71 kW bei einer empfohlenen Absicherung von 40A.