Kabelquerschnitt für 80 Ampere bei 120 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 80 A über 120 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)35 mm²Drop: 10.17V (2.54%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 11.74V (2.93%)
Voltage at Load389.8 VLine Loss: 1408.7 W
Max Power & Breaker55.43 kW80A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 80A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A237.22 V (59.31%)162.8 V391.3 V (97.83%)32870.4 WDrop High
2.5 mm²24 A18 A142.33 V (35.58%)257.7 V234.78 V (58.7%)19722.2 WDrop High
4 mm²32 A25 A88.96 V (22.24%)311.0 V146.74 V (36.68%)12326.4 WDrop High
6 mm²41 A32 A59.31 V (14.83%)340.7 V97.83 V (24.46%)8217.6 WDrop High
10 mm²57 A44 A35.58 V (8.9%)364.4 V58.7 V (14.67%)4930.6 WDrop High
16 mm²76 A59 A22.24 V (5.56%)377.8 V36.68 V (9.17%)3081.6 WDrop High
25 mm²101 A78 A14.23 V (3.56%)385.8 V23.48 V (5.87%)1972.2 W~ ≤5%
35 mm²125 A97 A10.17 V (2.54%)389.8 V16.77 V (4.19%)1408.7 W✓ OK (≤3%)
50 mm²151 A118 A7.12 V (1.78%)392.9 V11.74 V (2.93%)986.1 W✓ OK (≤3%)
70 mm²192 A150 A5.08 V (1.27%)394.9 V8.39 V (2.1%)704.4 W✓ OK (≤3%)
95 mm²232 A181 A3.75 V (0.94%)396.3 V6.18 V (1.54%)519.0 W✓ OK (≤3%)
120 mm²269 A210 A2.97 V (0.74%)397.0 V4.89 V (1.22%)410.9 W✓ OK (≤3%)
150 mm²309 A241 A2.37 V (0.59%)397.6 V3.91 V (0.98%)328.7 W✓ OK (≤3%)
185 mm²353 A275 A1.92 V (0.48%)398.1 V3.17 V (0.79%)266.5 W✓ OK (≤3%)
240 mm²415 A324 A1.48 V (0.37%)398.5 V2.45 V (0.61%)205.4 W✓ OK (≤3%)
300 mm²477 A372 A1.19 V (0.3%)398.8 V1.96 V (0.49%)164.4 W✓ OK (≤3%)
400 mm²570 A445 A0.89 V (0.22%)399.1 V1.47 V (0.37%)123.3 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 80 Ampere bei 120 Meter (400V)

Welcher Kabelquerschnitt wird für 80A bei 120m (400V) benötigt?

Für 80 Ampere über 120 Meter bei 400V wird ein Kupferkabel von 35 mm² empfohlen, um den Spannungsfall unter 3% (10.17V bzw. 2.54%) zu halten.

Wie hoch ist die maximale Leistung bei 80A und 400V?

Die übertragbare Leistung beträgt 55.43 kW bei einer empfohlenen Absicherung von 80A.