⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelquerschnitt für 40 Ampere bei 150 Meter (230V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 40 A über 150 m einfache Leitungslänge bei 230V.

Copper Cable (≤3% Drop)50 mm²Drop: 5.14V (2.23%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 6.05V (2.63%)
Voltage at Load224.9 VLine Loss: 205.4 W
Max Power & Breaker9.2 kW40A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 40A at 150m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A171.2 V (74.43%)58.8 V282.4 V (122.78%)6848.0 WDrop High
2.5 mm²24 A18 A102.72 V (44.66%)127.3 V169.44 V (73.67%)4108.8 WDrop High
4 mm²32 A25 A64.2 V (27.91%)165.8 V105.9 V (46.04%)2568.0 WDrop High
6 mm²41 A32 A42.8 V (18.61%)187.2 V70.6 V (30.7%)1712.0 WDrop High
10 mm²57 A44 A25.68 V (11.17%)204.3 V42.36 V (18.42%)1027.2 WDrop High
16 mm²76 A59 A16.05 V (6.98%)213.9 V26.48 V (11.51%)642.0 WDrop High
25 mm²101 A78 A10.27 V (4.47%)219.7 V16.94 V (7.37%)410.9 W~ ≤5%
35 mm²125 A97 A7.34 V (3.19%)222.7 V12.1 V (5.26%)293.5 W~ ≤5%
50 mm²151 A118 A5.14 V (2.23%)224.9 V8.47 V (3.68%)205.4 W✓ OK (≤3%)
70 mm²192 A150 A3.67 V (1.6%)226.3 V6.05 V (2.63%)146.7 W✓ OK (≤3%)
95 mm²232 A181 A2.7 V (1.18%)227.3 V4.46 V (1.94%)108.1 W✓ OK (≤3%)
120 mm²269 A210 A2.14 V (0.93%)227.9 V3.53 V (1.53%)85.6 W✓ OK (≤3%)
150 mm²309 A241 A1.71 V (0.74%)228.3 V2.82 V (1.23%)68.5 W✓ OK (≤3%)
185 mm²353 A275 A1.39 V (0.6%)228.6 V2.29 V (1.0%)55.5 W✓ OK (≤3%)
240 mm²415 A324 A1.07 V (0.47%)228.9 V1.76 V (0.77%)42.8 W✓ OK (≤3%)
300 mm²477 A372 A0.86 V (0.37%)229.1 V1.41 V (0.61%)34.2 W✓ OK (≤3%)
400 mm²570 A445 A0.64 V (0.28%)229.4 V1.06 V (0.46%)25.7 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 40 Ampere bei 150 Meter (230V)

Welcher Kabelquerschnitt wird für 40A bei 150m (230V) benötigt?

Für 40 Ampere über 150 Meter bei 230V wird ein Kupferkabel von 50 mm² empfohlen, um den Spannungsfall unter 3% (5.14V bzw. 2.23%) zu halten.

Wie hoch ist die maximale Leistung bei 40A und 230V?

Die übertragbare Leistung beträgt 9.2 kW bei einer empfohlenen Absicherung von 40A.