Kabelquerschnitt für 425 Ampere bei 175 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 425 A über 175 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)300 mm²Drop: 9.19V (2.3%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 11.37V (2.84%)
Voltage at Load390.8 VLine Loss: 6764.4 W
Max Power & Breaker294.45 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1837.85 V (459.46%)0.0 V3031.59 V (757.9%)1352881.2 WDrop High
2.5 mm²24 A18 A1102.71 V (275.68%)0.0 V1818.96 V (454.74%)811728.7 WDrop High
4 mm²32 A25 A689.19 V (172.3%)0.0 V1136.85 V (284.21%)507330.5 WDrop High
6 mm²41 A32 A459.46 V (114.87%)0.0 V757.9 V (189.47%)338220.3 WDrop High
10 mm²57 A44 A275.68 V (68.92%)124.3 V454.74 V (113.68%)202932.2 WDrop High
16 mm²76 A59 A172.3 V (43.07%)227.7 V284.21 V (71.05%)126832.6 WDrop High
25 mm²101 A78 A110.27 V (27.57%)289.7 V181.9 V (45.47%)81172.9 WDrop High
35 mm²125 A97 A78.77 V (19.69%)321.2 V129.93 V (32.48%)57980.6 WDrop High
50 mm²151 A118 A55.14 V (13.78%)344.9 V90.95 V (22.74%)40586.4 WDrop High
70 mm²192 A150 A39.38 V (9.85%)360.6 V64.96 V (16.24%)28990.3 WDrop High
95 mm²232 A181 A29.02 V (7.25%)371.0 V47.87 V (11.97%)21361.3 WDrop High
120 mm²269 A210 A22.97 V (5.74%)377.0 V37.89 V (9.47%)16911.0 WDrop High
150 mm²309 A241 A18.38 V (4.59%)381.6 V30.32 V (7.58%)13528.8 WDrop High
185 mm²353 A275 A14.9 V (3.73%)385.1 V24.58 V (6.15%)10969.3 WDrop High
240 mm²415 A324 A11.49 V (2.87%)388.5 V18.95 V (4.74%)8455.5 WDrop High
300 mm²477 A372 A9.19 V (2.3%)390.8 V15.16 V (3.79%)6764.4 W✓ OK (≤3%)
400 mm²570 A445 A6.89 V (1.72%)393.1 V11.37 V (2.84%)5073.3 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 425 Ampere bei 175 Meter (400V)

Welcher Kabelquerschnitt wird für 425A bei 175m (400V) benötigt?

Für 425 Ampere über 175 Meter bei 400V wird ein Kupferkabel von 300 mm² empfohlen, um den Spannungsfall unter 3% (9.19V bzw. 2.3%) zu halten.

Wie hoch ist die maximale Leistung bei 425A und 400V?

Die übertragbare Leistung beträgt 294.45 kW bei einer empfohlenen Absicherung von 450A.