⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelquerschnitt für 450 Ampere bei 175 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 450 A über 175 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)300 mm²Drop: 9.73V (2.43%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 12.04V (3.01%)
Voltage at Load390.3 VLine Loss: 7583.6 W
Max Power & Breaker311.77 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 450A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1945.96 V (486.49%)0.0 V3209.92 V (802.48%)1516725.0 WDrop High
2.5 mm²24 A18 A1167.58 V (291.89%)0.0 V1925.95 V (481.49%)910035.0 WDrop High
4 mm²32 A25 A729.73 V (182.43%)0.0 V1203.72 V (300.93%)568771.9 WDrop High
6 mm²41 A32 A486.49 V (121.62%)0.0 V802.48 V (200.62%)379181.2 WDrop High
10 mm²57 A44 A291.89 V (72.97%)108.1 V481.49 V (120.37%)227508.7 WDrop High
16 mm²76 A59 A182.43 V (45.61%)217.6 V300.93 V (75.23%)142193.0 WDrop High
25 mm²101 A78 A116.76 V (29.19%)283.2 V192.6 V (48.15%)91003.5 WDrop High
35 mm²125 A97 A83.4 V (20.85%)316.6 V137.57 V (34.39%)65002.5 WDrop High
50 mm²151 A118 A58.38 V (14.59%)341.6 V96.3 V (24.07%)45501.8 WDrop High
70 mm²192 A150 A41.7 V (10.42%)358.3 V68.78 V (17.2%)32501.2 WDrop High
95 mm²232 A181 A30.73 V (7.68%)369.3 V50.68 V (12.67%)23948.3 WDrop High
120 mm²269 A210 A24.32 V (6.08%)375.7 V40.12 V (10.03%)18959.1 WDrop High
150 mm²309 A241 A19.46 V (4.86%)380.5 V32.1 V (8.02%)15167.2 WDrop High
185 mm²353 A275 A15.78 V (3.94%)384.2 V26.03 V (6.51%)12297.8 WDrop High
240 mm²415 A324 A12.16 V (3.04%)387.8 V20.06 V (5.02%)9479.5 WDrop High
300 mm²477 A372 A9.73 V (2.43%)390.3 V16.05 V (4.01%)7583.6 W✓ OK (≤3%)
400 mm²570 A445 A7.3 V (1.82%)392.7 V12.04 V (3.01%)5687.7 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 450 Ampere bei 175 Meter (400V)

Welcher Kabelquerschnitt wird für 450A bei 175m (400V) benötigt?

Für 450 Ampere über 175 Meter bei 400V wird ein Kupferkabel von 300 mm² empfohlen, um den Spannungsfall unter 3% (9.73V bzw. 2.43%) zu halten.

Wie hoch ist die maximale Leistung bei 450A und 400V?

Die übertragbare Leistung beträgt 311.77 kW bei einer empfohlenen Absicherung von 450A.