Kabelquerschnitt für 500 Ampere bei 70 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 500 A über 70 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)400 mm²Drop: 3.24V (0.81%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 5.35V (1.34%)
Voltage at Load396.8 VLine Loss: 2808.8 W
Max Power & Breaker346.41 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 500A at 70m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A864.87 V (216.22%)0.0 V1426.63 V (356.66%)749000.0 WDrop High
2.5 mm²24 A18 A518.92 V (129.73%)0.0 V855.98 V (213.99%)449400.0 WDrop High
4 mm²32 A25 A324.33 V (81.08%)75.7 V534.99 V (133.75%)280875.0 WDrop High
6 mm²41 A32 A216.22 V (54.05%)183.8 V356.66 V (89.16%)187250.0 WDrop High
10 mm²57 A44 A129.73 V (32.43%)270.3 V213.99 V (53.5%)112350.0 WDrop High
16 mm²76 A59 A81.08 V (20.27%)318.9 V133.75 V (33.44%)70218.8 WDrop High
25 mm²101 A78 A51.89 V (12.97%)348.1 V85.6 V (21.4%)44940.0 WDrop High
35 mm²125 A97 A37.07 V (9.27%)362.9 V61.14 V (15.29%)32100.0 WDrop High
50 mm²151 A118 A25.95 V (6.49%)374.1 V42.8 V (10.7%)22470.0 WDrop High
70 mm²192 A150 A18.53 V (4.63%)381.5 V30.57 V (7.64%)16050.0 WDrop High
95 mm²232 A181 A13.66 V (3.41%)386.3 V22.53 V (5.63%)11826.3 WDrop High
120 mm²269 A210 A10.81 V (2.7%)389.2 V17.83 V (4.46%)9362.5 WDrop High
150 mm²309 A241 A8.65 V (2.16%)391.4 V14.27 V (3.57%)7490.0 WDrop High
185 mm²353 A275 A7.01 V (1.75%)393.0 V11.57 V (2.89%)6073.0 WDrop High
240 mm²415 A324 A5.41 V (1.35%)394.6 V8.92 V (2.23%)4681.2 WDrop High
300 mm²477 A372 A4.32 V (1.08%)395.7 V7.13 V (1.78%)3745.0 WDrop High
400 mm²570 A445 A3.24 V (0.81%)396.8 V5.35 V (1.34%)2808.8 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 500 Ampere bei 70 Meter (400V)

Welcher Kabelquerschnitt wird für 500A bei 70m (400V) benötigt?

Für 500 Ampere über 70 Meter bei 400V wird ein Kupferkabel von 400 mm² empfohlen, um den Spannungsfall unter 3% (3.24V bzw. 0.81%) zu halten.

Wie hoch ist die maximale Leistung bei 500A und 400V?

Die übertragbare Leistung beträgt 346.41 kW bei einer empfohlenen Absicherung von 500A.