Kabelquerschnitt für 25 Ampere bei 70 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 25 A über 70 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)6 mm²Drop: 10.81V (2.7%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 10.7V (2.67%)
Voltage at Load389.2 VLine Loss: 468.1 W
Max Power & Breaker17.32 kW25A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 25A at 70m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A43.24 V (10.81%)356.8 V71.33 V (17.83%)1872.5 WDrop High
2.5 mm²24 A18 A25.95 V (6.49%)374.1 V42.8 V (10.7%)1123.5 WDrop High
4 mm²32 A25 A16.22 V (4.05%)383.8 V26.75 V (6.69%)702.2 W~ ≤5%
6 mm²41 A32 A10.81 V (2.7%)389.2 V17.83 V (4.46%)468.1 W✓ OK (≤3%)
10 mm²57 A44 A6.49 V (1.62%)393.5 V10.7 V (2.67%)280.9 W✓ OK (≤3%)
16 mm²76 A59 A4.05 V (1.01%)395.9 V6.69 V (1.67%)175.5 W✓ OK (≤3%)
25 mm²101 A78 A2.59 V (0.65%)397.4 V4.28 V (1.07%)112.4 W✓ OK (≤3%)
35 mm²125 A97 A1.85 V (0.46%)398.1 V3.06 V (0.76%)80.2 W✓ OK (≤3%)
50 mm²151 A118 A1.3 V (0.32%)398.7 V2.14 V (0.53%)56.2 W✓ OK (≤3%)
70 mm²192 A150 A0.93 V (0.23%)399.1 V1.53 V (0.38%)40.1 W✓ OK (≤3%)
95 mm²232 A181 A0.68 V (0.17%)399.3 V1.13 V (0.28%)29.6 W✓ OK (≤3%)
120 mm²269 A210 A0.54 V (0.14%)399.5 V0.89 V (0.22%)23.4 W✓ OK (≤3%)
150 mm²309 A241 A0.43 V (0.11%)399.6 V0.71 V (0.18%)18.7 W✓ OK (≤3%)
185 mm²353 A275 A0.35 V (0.09%)399.6 V0.58 V (0.14%)15.2 W✓ OK (≤3%)
240 mm²415 A324 A0.27 V (0.07%)399.7 V0.45 V (0.11%)11.7 W✓ OK (≤3%)
300 mm²477 A372 A0.22 V (0.05%)399.8 V0.36 V (0.09%)9.4 W✓ OK (≤3%)
400 mm²570 A445 A0.16 V (0.04%)399.8 V0.27 V (0.07%)7.0 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 25 Ampere bei 70 Meter (400V)

Welcher Kabelquerschnitt wird für 25A bei 70m (400V) benötigt?

Für 25 Ampere über 70 Meter bei 400V wird ein Kupferkabel von 6 mm² empfohlen, um den Spannungsfall unter 3% (10.81V bzw. 2.7%) zu halten.

Wie hoch ist die maximale Leistung bei 25A und 400V?

Die übertragbare Leistung beträgt 17.32 kW bei einer empfohlenen Absicherung von 25A.