Kabelquerschnitt für 550 Ampere bei 400 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 550 A über 400 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 10.2V (2.55%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 33.63V (8.41%)
Voltage at Load389.8 VLine Loss: 9710.2 W
Max Power & Breaker381.05 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 400m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A5436.33 V (1359.08%)0.0 V8967.4 V (2241.85%)5178800.0 WDrop High
2.5 mm²24 A18 A3261.8 V (815.45%)0.0 V5380.44 V (1345.11%)3107280.0 WDrop High
4 mm²32 A25 A2038.62 V (509.66%)0.0 V3362.78 V (840.69%)1942050.0 WDrop High
6 mm²41 A32 A1359.08 V (339.77%)0.0 V2241.85 V (560.46%)1294700.0 WDrop High
10 mm²57 A44 A815.45 V (203.86%)0.0 V1345.11 V (336.28%)776820.0 WDrop High
16 mm²76 A59 A509.66 V (127.41%)0.0 V840.69 V (210.17%)485512.5 WDrop High
25 mm²101 A78 A326.18 V (81.54%)73.8 V538.04 V (134.51%)310728.0 WDrop High
35 mm²125 A97 A232.99 V (58.25%)167.0 V384.32 V (96.08%)221948.6 WDrop High
50 mm²151 A118 A163.09 V (40.77%)236.9 V269.02 V (67.26%)155364.0 WDrop High
70 mm²192 A150 A116.49 V (29.12%)283.5 V192.16 V (48.04%)110974.3 WDrop High
95 mm²232 A181 A85.84 V (21.46%)314.2 V141.59 V (35.4%)81770.5 WDrop High
120 mm²269 A210 A67.95 V (16.99%)332.0 V112.09 V (28.02%)64735.0 WDrop High
150 mm²309 A241 A54.36 V (13.59%)345.6 V89.67 V (22.42%)51788.0 WDrop High
185 mm²353 A275 A44.08 V (11.02%)355.9 V72.71 V (18.18%)41990.3 WDrop High
240 mm²415 A324 A33.98 V (8.49%)366.0 V56.05 V (14.01%)32367.5 WDrop High
300 mm²477 A372 A27.18 V (6.8%)372.8 V44.84 V (11.21%)25894.0 WDrop High
400 mm²570 A445 A20.39 V (5.1%)379.6 V33.63 V (8.41%)19420.5 WDrop High

FAQ — Kabelquerschnitt für 550 Ampere bei 400 Meter (400V)

Welcher Kabelquerschnitt wird für 550A bei 400m (400V) benötigt?

Für 550 Ampere über 400 Meter bei 400V wird ein Kupferkabel von 2× 400 mm² empfohlen, um den Spannungsfall unter 3% (10.2V bzw. 2.55%) zu halten.

Wie hoch ist die maximale Leistung bei 550A und 400V?

Die übertragbare Leistung beträgt 381.05 kW bei einer empfohlenen Absicherung von 600A.