Kabelquerschnitt für 550 Ampere bei 45 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 550 A über 45 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)400 mm²Drop: 2.29V (0.57%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 3.78V (0.95%)
Voltage at Load397.7 VLine Loss: 2184.8 W
Max Power & Breaker381.05 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A611.59 V (152.9%)0.0 V1008.83 V (252.21%)582615.0 WDrop High
2.5 mm²24 A18 A366.95 V (91.74%)33.0 V605.3 V (151.32%)349569.0 WDrop High
4 mm²32 A25 A229.35 V (57.34%)170.7 V378.31 V (94.58%)218480.6 WDrop High
6 mm²41 A32 A152.9 V (38.22%)247.1 V252.21 V (63.05%)145653.8 WDrop High
10 mm²57 A44 A91.74 V (22.93%)308.3 V151.32 V (37.83%)87392.2 WDrop High
16 mm²76 A59 A57.34 V (14.33%)342.7 V94.58 V (23.64%)54620.2 WDrop High
25 mm²101 A78 A36.7 V (9.17%)363.3 V60.53 V (15.13%)34956.9 WDrop High
35 mm²125 A97 A26.21 V (6.55%)373.8 V43.24 V (10.81%)24969.2 WDrop High
50 mm²151 A118 A18.35 V (4.59%)381.7 V30.26 V (7.57%)17478.5 WDrop High
70 mm²192 A150 A13.11 V (3.28%)386.9 V21.62 V (5.4%)12484.6 WDrop High
95 mm²232 A181 A9.66 V (2.41%)390.3 V15.93 V (3.98%)9199.2 WDrop High
120 mm²269 A210 A7.64 V (1.91%)392.4 V12.61 V (3.15%)7282.7 WDrop High
150 mm²309 A241 A6.12 V (1.53%)393.9 V10.09 V (2.52%)5826.1 WDrop High
185 mm²353 A275 A4.96 V (1.24%)395.0 V8.18 V (2.04%)4723.9 WDrop High
240 mm²415 A324 A3.82 V (0.96%)396.2 V6.31 V (1.58%)3641.3 WDrop High
300 mm²477 A372 A3.06 V (0.76%)396.9 V5.04 V (1.26%)2913.1 WDrop High
400 mm²570 A445 A2.29 V (0.57%)397.7 V3.78 V (0.95%)2184.8 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 550 Ampere bei 45 Meter (400V)

Welcher Kabelquerschnitt wird für 550A bei 45m (400V) benötigt?

Für 550 Ampere über 45 Meter bei 400V wird ein Kupferkabel von 400 mm² empfohlen, um den Spannungsfall unter 3% (2.29V bzw. 0.57%) zu halten.

Wie hoch ist die maximale Leistung bei 550A und 400V?

Die übertragbare Leistung beträgt 381.05 kW bei einer empfohlenen Absicherung von 600A.