Kabelquerschnitt für 60 Ampere bei 60 Meter (230V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 60 A über 60 m einfache Leitungslänge bei 230V.

Copper Cable (≤3% Drop)25 mm²Drop: 6.16V (2.68%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 5.08V (2.21%)
Voltage at Load223.8 VLine Loss: 369.8 W
Max Power & Breaker13.8 kW60A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 60A at 60m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A102.72 V (44.66%)127.3 V169.44 V (73.67%)6163.2 WDrop High
2.5 mm²24 A18 A61.63 V (26.8%)168.4 V101.66 V (44.2%)3697.9 WDrop High
4 mm²32 A25 A38.52 V (16.75%)191.5 V63.54 V (27.63%)2311.2 WDrop High
6 mm²41 A32 A25.68 V (11.17%)204.3 V42.36 V (18.42%)1540.8 WDrop High
10 mm²57 A44 A15.41 V (6.7%)214.6 V25.42 V (11.05%)924.5 WDrop High
16 mm²76 A59 A9.63 V (4.19%)220.4 V15.88 V (6.91%)577.8 W~ ≤5%
25 mm²101 A78 A6.16 V (2.68%)223.8 V10.17 V (4.42%)369.8 W✓ OK (≤3%)
35 mm²125 A97 A4.4 V (1.91%)225.6 V7.26 V (3.16%)264.1 W✓ OK (≤3%)
50 mm²151 A118 A3.08 V (1.34%)226.9 V5.08 V (2.21%)184.9 W✓ OK (≤3%)
70 mm²192 A150 A2.2 V (0.96%)227.8 V3.63 V (1.58%)132.1 W✓ OK (≤3%)
95 mm²232 A181 A1.62 V (0.71%)228.4 V2.68 V (1.16%)97.3 W✓ OK (≤3%)
120 mm²269 A210 A1.28 V (0.56%)228.7 V2.12 V (0.92%)77.0 W✓ OK (≤3%)
150 mm²309 A241 A1.03 V (0.45%)229.0 V1.69 V (0.74%)61.6 W✓ OK (≤3%)
185 mm²353 A275 A0.83 V (0.36%)229.2 V1.37 V (0.6%)50.0 W✓ OK (≤3%)
240 mm²415 A324 A0.64 V (0.28%)229.4 V1.06 V (0.46%)38.5 W✓ OK (≤3%)
300 mm²477 A372 A0.51 V (0.22%)229.5 V0.85 V (0.37%)30.8 W✓ OK (≤3%)
400 mm²570 A445 A0.39 V (0.17%)229.6 V0.64 V (0.28%)23.1 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 60 Ampere bei 60 Meter (230V)

Welcher Kabelquerschnitt wird für 60A bei 60m (230V) benötigt?

Für 60 Ampere über 60 Meter bei 230V wird ein Kupferkabel von 25 mm² empfohlen, um den Spannungsfall unter 3% (6.16V bzw. 2.68%) zu halten.

Wie hoch ist die maximale Leistung bei 60A und 230V?

Die übertragbare Leistung beträgt 13.8 kW bei einer empfohlenen Absicherung von 60A.