Kabelquerschnitt für 63 Ampere bei 500 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 63 A über 500 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)120 mm²Drop: 9.73V (2.43%)
Aluminum Cable (≤3% Drop)185 mm²Drop: 10.41V (2.6%)
Voltage at Load390.3 VLine Loss: 1061.7 W
Max Power & Breaker43.65 kW63A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 63A at 500m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A778.38 V (194.6%)0.0 V1283.97 V (320.99%)84936.6 WDrop High
2.5 mm²24 A18 A467.03 V (116.76%)0.0 V770.38 V (192.6%)50962.0 WDrop High
4 mm²32 A25 A291.89 V (72.97%)108.1 V481.49 V (120.37%)31851.2 WDrop High
6 mm²41 A32 A194.6 V (48.65%)205.4 V320.99 V (80.25%)21234.1 WDrop High
10 mm²57 A44 A116.76 V (29.19%)283.2 V192.6 V (48.15%)12740.5 WDrop High
16 mm²76 A59 A72.97 V (18.24%)327.0 V120.37 V (30.09%)7962.8 WDrop High
25 mm²101 A78 A46.7 V (11.68%)353.3 V77.04 V (19.26%)5096.2 WDrop High
35 mm²125 A97 A33.36 V (8.34%)366.6 V55.03 V (13.76%)3640.1 WDrop High
50 mm²151 A118 A23.35 V (5.84%)376.6 V38.52 V (9.63%)2548.1 WDrop High
70 mm²192 A150 A16.68 V (4.17%)383.3 V27.51 V (6.88%)1820.1 W~ ≤5%
95 mm²232 A181 A12.29 V (3.07%)387.7 V20.27 V (5.07%)1341.1 W~ ≤5%
120 mm²269 A210 A9.73 V (2.43%)390.3 V16.05 V (4.01%)1061.7 W✓ OK (≤3%)
150 mm²309 A241 A7.78 V (1.95%)392.2 V12.84 V (3.21%)849.4 W✓ OK (≤3%)
185 mm²353 A275 A6.31 V (1.58%)393.7 V10.41 V (2.6%)688.7 W✓ OK (≤3%)
240 mm²415 A324 A4.86 V (1.22%)395.1 V8.02 V (2.01%)530.9 W✓ OK (≤3%)
300 mm²477 A372 A3.89 V (0.97%)396.1 V6.42 V (1.6%)424.7 W✓ OK (≤3%)
400 mm²570 A445 A2.92 V (0.73%)397.1 V4.81 V (1.2%)318.5 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 63 Ampere bei 500 Meter (400V)

Welcher Kabelquerschnitt wird für 63A bei 500m (400V) benötigt?

Für 63 Ampere über 500 Meter bei 400V wird ein Kupferkabel von 120 mm² empfohlen, um den Spannungsfall unter 3% (9.73V bzw. 2.43%) zu halten.

Wie hoch ist die maximale Leistung bei 63A und 400V?

Die übertragbare Leistung beträgt 43.65 kW bei einer empfohlenen Absicherung von 63A.