Kabelquerschnitt für 20 Ampere bei 500 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 20 A über 500 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)35 mm²Drop: 10.59V (2.65%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 8.73V (2.18%)
Voltage at Load389.4 VLine Loss: 366.9 W
Max Power & Breaker13.86 kW20A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 20A at 500m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A247.11 V (61.78%)152.9 V407.61 V (101.9%)8560.0 WDrop High
2.5 mm²24 A18 A148.26 V (37.07%)251.7 V244.57 V (61.14%)5136.0 WDrop High
4 mm²32 A25 A92.66 V (23.17%)307.3 V152.85 V (38.21%)3210.0 WDrop High
6 mm²41 A32 A61.78 V (15.44%)338.2 V101.9 V (25.48%)2140.0 WDrop High
10 mm²57 A44 A37.07 V (9.27%)362.9 V61.14 V (15.29%)1284.0 WDrop High
16 mm²76 A59 A23.17 V (5.79%)376.8 V38.21 V (9.55%)802.5 WDrop High
25 mm²101 A78 A14.83 V (3.71%)385.2 V24.46 V (6.11%)513.6 W~ ≤5%
35 mm²125 A97 A10.59 V (2.65%)389.4 V17.47 V (4.37%)366.9 W✓ OK (≤3%)
50 mm²151 A118 A7.41 V (1.85%)392.6 V12.23 V (3.06%)256.8 W✓ OK (≤3%)
70 mm²192 A150 A5.3 V (1.32%)394.7 V8.73 V (2.18%)183.4 W✓ OK (≤3%)
95 mm²232 A181 A3.9 V (0.98%)396.1 V6.44 V (1.61%)135.2 W✓ OK (≤3%)
120 mm²269 A210 A3.09 V (0.77%)396.9 V5.1 V (1.27%)107.0 W✓ OK (≤3%)
150 mm²309 A241 A2.47 V (0.62%)397.5 V4.08 V (1.02%)85.6 W✓ OK (≤3%)
185 mm²353 A275 A2.0 V (0.5%)398.0 V3.3 V (0.83%)69.4 W✓ OK (≤3%)
240 mm²415 A324 A1.54 V (0.39%)398.5 V2.55 V (0.64%)53.5 W✓ OK (≤3%)
300 mm²477 A372 A1.24 V (0.31%)398.8 V2.04 V (0.51%)42.8 W✓ OK (≤3%)
400 mm²570 A445 A0.93 V (0.23%)399.1 V1.53 V (0.38%)32.1 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 20 Ampere bei 500 Meter (400V)

Welcher Kabelquerschnitt wird für 20A bei 500m (400V) benötigt?

Für 20 Ampere über 500 Meter bei 400V wird ein Kupferkabel von 35 mm² empfohlen, um den Spannungsfall unter 3% (10.59V bzw. 2.65%) zu halten.

Wie hoch ist die maximale Leistung bei 20A und 400V?

Die übertragbare Leistung beträgt 13.86 kW bei einer empfohlenen Absicherung von 20A.