Kabelquerschnitt für 70 Ampere bei 70 Meter (230V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 70 A über 70 m einfache Leitungslänge bei 230V.

Copper Cable (≤3% Drop)35 mm²Drop: 5.99V (2.61%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 4.94V (2.15%)
Voltage at Load224.0 VLine Loss: 419.4 W
Max Power & Breaker16.1 kW70A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 70A at 70m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A139.81 V (60.79%)90.2 V230.63 V (100.27%)9786.9 WDrop High
2.5 mm²24 A18 A83.89 V (36.47%)146.1 V138.38 V (60.16%)5872.2 WDrop High
4 mm²32 A25 A52.43 V (22.8%)177.6 V86.48 V (37.6%)3670.1 WDrop High
6 mm²41 A32 A34.95 V (15.2%)195.0 V57.66 V (25.07%)2446.7 WDrop High
10 mm²57 A44 A20.97 V (9.12%)209.0 V34.59 V (15.04%)1468.0 WDrop High
16 mm²76 A59 A13.11 V (5.7%)216.9 V21.62 V (9.4%)917.5 WDrop High
25 mm²101 A78 A8.39 V (3.65%)221.6 V13.84 V (6.02%)587.2 W~ ≤5%
35 mm²125 A97 A5.99 V (2.61%)224.0 V9.88 V (4.3%)419.4 W✓ OK (≤3%)
50 mm²151 A118 A4.19 V (1.82%)225.8 V6.92 V (3.01%)293.6 W✓ OK (≤3%)
70 mm²192 A150 A3.0 V (1.3%)227.0 V4.94 V (2.15%)209.7 W✓ OK (≤3%)
95 mm²232 A181 A2.21 V (0.96%)227.8 V3.64 V (1.58%)154.5 W✓ OK (≤3%)
120 mm²269 A210 A1.75 V (0.76%)228.3 V2.88 V (1.25%)122.3 W✓ OK (≤3%)
150 mm²309 A241 A1.4 V (0.61%)228.6 V2.31 V (1.0%)97.9 W✓ OK (≤3%)
185 mm²353 A275 A1.13 V (0.49%)228.9 V1.87 V (0.81%)79.4 W✓ OK (≤3%)
240 mm²415 A324 A0.87 V (0.38%)229.1 V1.44 V (0.63%)61.2 W✓ OK (≤3%)
300 mm²477 A372 A0.7 V (0.3%)229.3 V1.15 V (0.5%)48.9 W✓ OK (≤3%)
400 mm²570 A445 A0.52 V (0.23%)229.5 V0.86 V (0.38%)36.7 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 70 Ampere bei 70 Meter (230V)

Welcher Kabelquerschnitt wird für 70A bei 70m (230V) benötigt?

Für 70 Ampere über 70 Meter bei 230V wird ein Kupferkabel von 35 mm² empfohlen, um den Spannungsfall unter 3% (5.99V bzw. 2.61%) zu halten.

Wie hoch ist die maximale Leistung bei 70A und 230V?

Die übertragbare Leistung beträgt 16.1 kW bei einer empfohlenen Absicherung von 70A.