Kabelquerschnitt für 700 Ampere bei 90 Meter (230V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 700 A über 90 m einfache Leitungslänge bei 230V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 3.37V (1.47%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 11.12V (4.83%)
Voltage at Load226.6 VLine Loss: 2359.3 W
Max Power & Breaker161.0 kW700A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 700A at 90m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1797.6 V (781.57%)0.0 V2965.2 V (1289.22%)1258320.0 WDrop High
2.5 mm²24 A18 A1078.56 V (468.94%)0.0 V1779.12 V (773.53%)754992.0 WDrop High
4 mm²32 A25 A674.1 V (293.09%)0.0 V1111.95 V (483.46%)471870.0 WDrop High
6 mm²41 A32 A449.4 V (195.39%)0.0 V741.3 V (322.3%)314580.0 WDrop High
10 mm²57 A44 A269.64 V (117.23%)0.0 V444.78 V (193.38%)188748.0 WDrop High
16 mm²76 A59 A168.53 V (73.27%)61.5 V277.99 V (120.86%)117967.5 WDrop High
25 mm²101 A78 A107.86 V (46.89%)122.1 V177.91 V (77.35%)75499.2 WDrop High
35 mm²125 A97 A77.04 V (33.5%)153.0 V127.08 V (55.25%)53928.0 WDrop High
50 mm²151 A118 A53.93 V (23.45%)176.1 V88.96 V (38.68%)37749.6 WDrop High
70 mm²192 A150 A38.52 V (16.75%)191.5 V63.54 V (27.63%)26964.0 WDrop High
95 mm²232 A181 A28.38 V (12.34%)201.6 V46.82 V (20.36%)19868.2 WDrop High
120 mm²269 A210 A22.47 V (9.77%)207.5 V37.06 V (16.12%)15729.0 WDrop High
150 mm²309 A241 A17.98 V (7.82%)212.0 V29.65 V (12.89%)12583.2 WDrop High
185 mm²353 A275 A14.58 V (6.34%)215.4 V24.04 V (10.45%)10202.6 WDrop High
240 mm²415 A324 A11.23 V (4.88%)218.8 V18.53 V (8.06%)7864.5 WDrop High
300 mm²477 A372 A8.99 V (3.91%)221.0 V14.83 V (6.45%)6291.6 WDrop High
400 mm²570 A445 A6.74 V (2.93%)223.3 V11.12 V (4.83%)4718.7 WDrop High

FAQ — Kabelquerschnitt für 700 Ampere bei 90 Meter (230V)

Welcher Kabelquerschnitt wird für 700A bei 90m (230V) benötigt?

Für 700 Ampere über 90 Meter bei 230V wird ein Kupferkabel von 2× 400 mm² empfohlen, um den Spannungsfall unter 3% (3.37V bzw. 1.47%) zu halten.

Wie hoch ist die maximale Leistung bei 700A und 230V?

Die übertragbare Leistung beträgt 161.0 kW bei einer empfohlenen Absicherung von 700A.