Kabelquerschnitt für 900 Ampere bei 350 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 900 A über 350 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)3× 400 mm²Drop: 9.73V (2.43%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 48.15V (12.04%)
Voltage at Load390.3 VLine Loss: 15167.3 W
Max Power & Breaker623.54 kW1000A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 900A at 350m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A7783.84 V (1945.96%)0.0 V12839.69 V (3209.92%)12133800.0 WDrop High
2.5 mm²24 A18 A4670.3 V (1167.58%)0.0 V7703.82 V (1925.95%)7280280.0 WDrop High
4 mm²32 A25 A2918.94 V (729.73%)0.0 V4814.88 V (1203.72%)4550175.0 WDrop High
6 mm²41 A32 A1945.96 V (486.49%)0.0 V3209.92 V (802.48%)3033450.0 WDrop High
10 mm²57 A44 A1167.58 V (291.89%)0.0 V1925.95 V (481.49%)1820070.0 WDrop High
16 mm²76 A59 A729.73 V (182.43%)0.0 V1203.72 V (300.93%)1137543.8 WDrop High
25 mm²101 A78 A467.03 V (116.76%)0.0 V770.38 V (192.6%)728028.0 WDrop High
35 mm²125 A97 A333.59 V (83.4%)66.4 V550.27 V (137.57%)520020.0 WDrop High
50 mm²151 A118 A233.52 V (58.38%)166.5 V385.19 V (96.3%)364014.0 WDrop High
70 mm²192 A150 A166.8 V (41.7%)233.2 V275.14 V (68.78%)260010.0 WDrop High
95 mm²232 A181 A122.9 V (30.73%)277.1 V202.73 V (50.68%)191586.3 WDrop High
120 mm²269 A210 A97.3 V (24.32%)302.7 V160.5 V (40.12%)151672.5 WDrop High
150 mm²309 A241 A77.84 V (19.46%)322.2 V128.4 V (32.1%)121338.0 WDrop High
185 mm²353 A275 A63.11 V (15.78%)336.9 V104.11 V (26.03%)98382.2 WDrop High
240 mm²415 A324 A48.65 V (12.16%)351.4 V80.25 V (20.06%)75836.2 WDrop High
300 mm²477 A372 A38.92 V (9.73%)361.1 V64.2 V (16.05%)60669.0 WDrop High
400 mm²570 A445 A29.19 V (7.3%)370.8 V48.15 V (12.04%)45501.8 WDrop High

FAQ — Kabelquerschnitt für 900 Ampere bei 350 Meter (400V)

Welcher Kabelquerschnitt wird für 900A bei 350m (400V) benötigt?

Für 900 Ampere über 350 Meter bei 400V wird ein Kupferkabel von 3× 400 mm² empfohlen, um den Spannungsfall unter 3% (9.73V bzw. 2.43%) zu halten.

Wie hoch ist die maximale Leistung bei 900A und 400V?

Die übertragbare Leistung beträgt 623.54 kW bei einer empfohlenen Absicherung von 1000A.