10 kVA to Amps at 230V Single-Phase AC (IEC)

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 10 kVA on a 230V Single-Phase AC (IEC) circuit.

Line Current (0.85 PF)43.48 AAt 1.0 PF: 43.48 A
Active / Apparent Power8.5 kW10.0 kVA · 5.27 kVAR
Recommended Breaker60 A (NEC)45 A (IEC Nominal)
Recommended Copper Wire8 AWGIEC Metric: 10 mm²

Engineering Breakdown for 10 kVA at 230V

Input Rating10 kVA (230V Single-Phase AC (IEC))
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)43.48 Amps
Amperage at 1.00 Power Factor (Resistive Load)43.48 Amps
Real Power (kW / Watts)8.5 kW (8,500 W)
Apparent Power (kVA) & Reactive Power (kVAR)10.0 kVA / 5.27 kVAR
Equivalent Mechanical Horsepower (HP)11.4 HP
NEC 125% Continuous Circuit Breaker60 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)8 AWG (NEC) / 10 mm² (IEC)

Frequently Asked Questions

How many amps is 10 kVA at 230V (1-Phase)?

At 230V Single-Phase AC (IEC), 10 kVA equals 43.48 Amps at an industrial power factor of 0.85 (or 43.48 Amps at unity power factor 1.0).

What size breaker and wire is needed for 10 kVA at 230V?

For 43.48A continuous load, NEC requires a 125% rated breaker of 60A with 8 AWG copper conductors, while IEC standard sizing uses a 45A breaker with 10 mm² copper cable.