4 kVA to Amps at 208V Single-Phase AC

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 4 kVA on a 208V Single-Phase AC circuit.

Line Current (0.85 PF)19.23 AAt 1.0 PF: 19.23 A
Active / Apparent Power3.4 kW4.0 kVA · 2.11 kVAR
Recommended Breaker25 A (NEC)20 A (IEC Nominal)
Recommended Copper Wire10 AWGIEC Metric: 4 mm²

Engineering Breakdown for 4 kVA at 208V

Input Rating4 kVA (208V Single-Phase AC)
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)19.23 Amps
Amperage at 1.00 Power Factor (Resistive Load)19.23 Amps
Real Power (kW / Watts)3.4 kW (3,400 W)
Apparent Power (kVA) & Reactive Power (kVAR)4.0 kVA / 2.11 kVAR
Equivalent Mechanical Horsepower (HP)4.56 HP
NEC 125% Continuous Circuit Breaker25 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)10 AWG (NEC) / 4 mm² (IEC)

Frequently Asked Questions

How many amps is 4 kVA at 208V (1-Phase)?

At 208V Single-Phase AC, 4 kVA equals 19.23 Amps at an industrial power factor of 0.85 (or 19.23 Amps at unity power factor 1.0).

What size breaker and wire is needed for 4 kVA at 208V?

For 19.23A continuous load, NEC requires a 125% rated breaker of 25A with 10 AWG copper conductors, while IEC standard sizing uses a 20A breaker with 4 mm² copper cable.