46 kVA to Amps at 400V Three-Phase AC (IEC Europe)

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 46 kVA on a 400V Three-Phase AC (IEC Europe) circuit.

Line Current (0.85 PF)66.4 AAt 1.0 PF: 66.4 A
Active / Apparent Power39.1 kW46.0 kVA · 24.23 kVAR
Recommended Breaker90 A (NEC)70 A (IEC Nominal)
Recommended Copper Wire4 AWGIEC Metric: 16 mm²

Engineering Breakdown for 46 kVA at 400V

Input Rating46 kVA (400V Three-Phase AC (IEC Europe))
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)66.4 Amps
Amperage at 1.00 Power Factor (Resistive Load)66.4 Amps
Real Power (kW / Watts)39.1 kW (39,100 W)
Apparent Power (kVA) & Reactive Power (kVAR)46.0 kVA / 24.23 kVAR
Equivalent Mechanical Horsepower (HP)52.43 HP
NEC 125% Continuous Circuit Breaker90 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)4 AWG (NEC) / 16 mm² (IEC)

Frequently Asked Questions

How many amps is 46 kVA at 400V (3-Phase)?

At 400V Three-Phase AC (IEC Europe), 46 kVA equals 66.4 Amps at an industrial power factor of 0.85 (or 66.4 Amps at unity power factor 1.0).

What size breaker and wire is needed for 46 kVA at 400V?

For 66.4A continuous load, NEC requires a 125% rated breaker of 90A with 4 AWG copper conductors, while IEC standard sizing uses a 70A breaker with 16 mm² copper cable.