⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🏭 Industrial Electrical Conversion · Three-Phase & Single-Phase

6 kVA to Amps at 230V Three-Phase AC

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 6 kVA on a 230V Three-Phase AC circuit.

Line Current (0.85 PF)15.06 AAt 1.0 PF: 15.06 A
Active / Apparent Power5.1 kW6.0 kVA · 3.16 kVAR
Recommended Breaker20 A (NEC)16 A (IEC Nominal)
Recommended Copper Wire12 AWGIEC Metric: 1.5 mm²

Engineering Breakdown for 6 kVA at 230V

Input Rating6 kVA (230V Three-Phase AC)
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)15.06 Amps
Amperage at 1.00 Power Factor (Resistive Load)15.06 Amps
Real Power (kW / Watts)5.1 kW (5,100 W)
Apparent Power (kVA) & Reactive Power (kVAR)6.0 kVA / 3.16 kVAR
Equivalent Mechanical Horsepower (HP)6.84 HP
NEC 125% Continuous Circuit Breaker20 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)12 AWG (NEC) / 1.5 mm² (IEC)

Frequently Asked Questions

How many amps is 6 kVA at 230V (3-Phase)?

At 230V Three-Phase AC, 6 kVA equals 15.06 Amps at an industrial power factor of 0.85 (or 15.06 Amps at unity power factor 1.0).

What size breaker and wire is needed for 6 kVA at 230V?

For 15.06A continuous load, NEC requires a 125% rated breaker of 20A with 12 AWG copper conductors, while IEC standard sizing uses a 16A breaker with 1.5 mm² copper cable.