6 kVA to Amps at 230V Single-Phase AC (IEC)

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 6 kVA on a 230V Single-Phase AC (IEC) circuit.

Line Current (0.85 PF)26.09 AAt 1.0 PF: 26.09 A
Active / Apparent Power5.1 kW6.0 kVA · 3.16 kVAR
Recommended Breaker35 A (NEC)30 A (IEC Nominal)
Recommended Copper Wire10 AWGIEC Metric: 6 mm²

Engineering Breakdown for 6 kVA at 230V

Input Rating6 kVA (230V Single-Phase AC (IEC))
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)26.09 Amps
Amperage at 1.00 Power Factor (Resistive Load)26.09 Amps
Real Power (kW / Watts)5.1 kW (5,100 W)
Apparent Power (kVA) & Reactive Power (kVAR)6.0 kVA / 3.16 kVAR
Equivalent Mechanical Horsepower (HP)6.84 HP
NEC 125% Continuous Circuit Breaker35 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)10 AWG (NEC) / 6 mm² (IEC)

Frequently Asked Questions

How many amps is 6 kVA at 230V (1-Phase)?

At 230V Single-Phase AC (IEC), 6 kVA equals 26.09 Amps at an industrial power factor of 0.85 (or 26.09 Amps at unity power factor 1.0).

What size breaker and wire is needed for 6 kVA at 230V?

For 26.09A continuous load, NEC requires a 125% rated breaker of 35A with 10 AWG copper conductors, while IEC standard sizing uses a 30A breaker with 6 mm² copper cable.