1.5 kW to Amps at 120V Single-Phase AC

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 1.5 kW on a 120V Single-Phase AC circuit.

Line Current (0.85 PF)14.71 AAt 1.0 PF: 12.5 A
Active / Apparent Power1.5 kW1.76 kVA · 0.93 kVAR
Recommended Breaker20 A (NEC)15 A (IEC Nominal)
Recommended Copper Wire12 AWGIEC Metric: 4 mm²

Engineering Breakdown for 1.5 kW at 120V

Input Rating1.5 kW (120V Single-Phase AC)
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)14.71 Amps
Amperage at 1.00 Power Factor (Resistive Load)12.5 Amps
Real Power (kW / Watts)1.5 kW (1,500 W)
Apparent Power (kVA) & Reactive Power (kVAR)1.76 kVA / 0.93 kVAR
Equivalent Mechanical Horsepower (HP)2.01 HP
NEC 125% Continuous Circuit Breaker20 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)12 AWG (NEC) / 4 mm² (IEC)

Frequently Asked Questions

How many amps is 1.5 kW at 120V (1-Phase)?

At 120V Single-Phase AC, 1.5 kW equals 14.71 Amps at an industrial power factor of 0.85 (or 12.5 Amps at unity power factor 1.0).

What size breaker and wire is needed for 1.5 kW at 120V?

For 14.71A continuous load, NEC requires a 125% rated breaker of 20A with 12 AWG copper conductors, while IEC standard sizing uses a 15A breaker with 4 mm² copper cable.