1.5 kW to Amps at 208V Three-Phase AC

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 1.5 kW on a 208V Three-Phase AC circuit.

Line Current (0.85 PF)4.9 AAt 1.0 PF: 4.16 A
Active / Apparent Power1.5 kW1.76 kVA · 0.93 kVAR
Recommended Breaker10 A (NEC)6 A (IEC Nominal)
Recommended Copper Wire14 AWGIEC Metric: 1.5 mm²

Engineering Breakdown for 1.5 kW at 208V

Input Rating1.5 kW (208V Three-Phase AC)
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)4.9 Amps
Amperage at 1.00 Power Factor (Resistive Load)4.16 Amps
Real Power (kW / Watts)1.5 kW (1,500 W)
Apparent Power (kVA) & Reactive Power (kVAR)1.76 kVA / 0.93 kVAR
Equivalent Mechanical Horsepower (HP)2.01 HP
NEC 125% Continuous Circuit Breaker10 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)14 AWG (NEC) / 1.5 mm² (IEC)

Frequently Asked Questions

How many amps is 1.5 kW at 208V (3-Phase)?

At 208V Three-Phase AC, 1.5 kW equals 4.9 Amps at an industrial power factor of 0.85 (or 4.16 Amps at unity power factor 1.0).

What size breaker and wire is needed for 1.5 kW at 208V?

For 4.9A continuous load, NEC requires a 125% rated breaker of 10A with 14 AWG copper conductors, while IEC standard sizing uses a 6A breaker with 1.5 mm² copper cable.