⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🏭 Industrial Electrical Conversion · Three-Phase & Single-Phase

118 kW to Amps at 600V Three-Phase AC (Canada / Heavy)

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 118 kW on a 600V Three-Phase AC (Canada / Heavy) circuit.

Line Current (0.85 PF)133.58 AAt 1.0 PF: 113.55 A
Active / Apparent Power118.0 kW138.82 kVA · 73.13 kVAR
Recommended Breaker175 A (NEC)150 A (IEC Nominal)
Recommended Copper Wire1/0 AWGIEC Metric: 50 mm²

Engineering Breakdown for 118 kW at 600V

Input Rating118 kW (600V Three-Phase AC (Canada / Heavy))
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)133.58 Amps
Amperage at 1.00 Power Factor (Resistive Load)113.55 Amps
Real Power (kW / Watts)118.0 kW (118,000 W)
Apparent Power (kVA) & Reactive Power (kVAR)138.82 kVA / 73.13 kVAR
Equivalent Mechanical Horsepower (HP)158.24 HP
NEC 125% Continuous Circuit Breaker175 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)1/0 AWG (NEC) / 50 mm² (IEC)

Frequently Asked Questions

How many amps is 118 kW at 600V (3-Phase)?

At 600V Three-Phase AC (Canada / Heavy), 118 kW equals 133.58 Amps at an industrial power factor of 0.85 (or 113.55 Amps at unity power factor 1.0).

What size breaker and wire is needed for 118 kW at 600V?

For 133.58A continuous load, NEC requires a 125% rated breaker of 175A with 1/0 AWG copper conductors, while IEC standard sizing uses a 150A breaker with 50 mm² copper cable.