25 kW to Amps at 600V Three-Phase AC (Canada / Heavy)

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 25 kW on a 600V Three-Phase AC (Canada / Heavy) circuit.

Line Current (0.85 PF)28.3 AAt 1.0 PF: 24.06 A
Active / Apparent Power25.0 kW29.41 kVA · 15.49 kVAR
Recommended Breaker40 A (NEC)30 A (IEC Nominal)
Recommended Copper Wire10 AWGIEC Metric: 4 mm²

Engineering Breakdown for 25 kW at 600V

Input Rating25 kW (600V Three-Phase AC (Canada / Heavy))
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)28.3 Amps
Amperage at 1.00 Power Factor (Resistive Load)24.06 Amps
Real Power (kW / Watts)25.0 kW (25,000 W)
Apparent Power (kVA) & Reactive Power (kVAR)29.41 kVA / 15.49 kVAR
Equivalent Mechanical Horsepower (HP)33.53 HP
NEC 125% Continuous Circuit Breaker40 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)10 AWG (NEC) / 4 mm² (IEC)

Frequently Asked Questions

How many amps is 25 kW at 600V (3-Phase)?

At 600V Three-Phase AC (Canada / Heavy), 25 kW equals 28.3 Amps at an industrial power factor of 0.85 (or 24.06 Amps at unity power factor 1.0).

What size breaker and wire is needed for 25 kW at 600V?

For 28.3A continuous load, NEC requires a 125% rated breaker of 40A with 10 AWG copper conductors, while IEC standard sizing uses a 30A breaker with 4 mm² copper cable.