17.5 kW to Amps at 230V Single-Phase AC (IEC)

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 17.5 kW on a 230V Single-Phase AC (IEC) circuit.

Line Current (0.85 PF)89.51 AAt 1.0 PF: 76.09 A
Active / Apparent Power17.5 kW20.59 kVA · 10.85 kVAR
Recommended Breaker125 A (NEC)90 A (IEC Nominal)
Recommended Copper Wire3 AWGIEC Metric: 25 mm²

Engineering Breakdown for 17.5 kW at 230V

Input Rating17.5 kW (230V Single-Phase AC (IEC))
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)89.51 Amps
Amperage at 1.00 Power Factor (Resistive Load)76.09 Amps
Real Power (kW / Watts)17.5 kW (17,500 W)
Apparent Power (kVA) & Reactive Power (kVAR)20.59 kVA / 10.85 kVAR
Equivalent Mechanical Horsepower (HP)23.47 HP
NEC 125% Continuous Circuit Breaker125 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)3 AWG (NEC) / 25 mm² (IEC)

Frequently Asked Questions

How many amps is 17.5 kW at 230V (1-Phase)?

At 230V Single-Phase AC (IEC), 17.5 kW equals 89.51 Amps at an industrial power factor of 0.85 (or 76.09 Amps at unity power factor 1.0).

What size breaker and wire is needed for 17.5 kW at 230V?

For 89.51A continuous load, NEC requires a 125% rated breaker of 125A with 3 AWG copper conductors, while IEC standard sizing uses a 90A breaker with 25 mm² copper cable.