18.5 kW to Amps at 230V Single-Phase AC (IEC)

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 18.5 kW on a 230V Single-Phase AC (IEC) circuit.

Line Current (0.85 PF)94.63 AAt 1.0 PF: 80.43 A
Active / Apparent Power18.5 kW21.76 kVA · 11.47 kVAR
Recommended Breaker125 A (NEC)100 A (IEC Nominal)
Recommended Copper Wire3 AWGIEC Metric: 25 mm²

Engineering Breakdown for 18.5 kW at 230V

Input Rating18.5 kW (230V Single-Phase AC (IEC))
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)94.63 Amps
Amperage at 1.00 Power Factor (Resistive Load)80.43 Amps
Real Power (kW / Watts)18.5 kW (18,500 W)
Apparent Power (kVA) & Reactive Power (kVAR)21.76 kVA / 11.47 kVAR
Equivalent Mechanical Horsepower (HP)24.81 HP
NEC 125% Continuous Circuit Breaker125 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)3 AWG (NEC) / 25 mm² (IEC)

Frequently Asked Questions

How many amps is 18.5 kW at 230V (1-Phase)?

At 230V Single-Phase AC (IEC), 18.5 kW equals 94.63 Amps at an industrial power factor of 0.85 (or 80.43 Amps at unity power factor 1.0).

What size breaker and wire is needed for 18.5 kW at 230V?

For 94.63A continuous load, NEC requires a 125% rated breaker of 125A with 3 AWG copper conductors, while IEC standard sizing uses a 100A breaker with 25 mm² copper cable.