18.5 kW to Amps at 600V Three-Phase AC (Canada / Heavy)

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 18.5 kW on a 600V Three-Phase AC (Canada / Heavy) circuit.

Line Current (0.85 PF)20.94 AAt 1.0 PF: 17.8 A
Active / Apparent Power18.5 kW21.76 kVA · 11.47 kVAR
Recommended Breaker30 A (NEC)25 A (IEC Nominal)
Recommended Copper Wire10 AWGIEC Metric: 2.5 mm²

Engineering Breakdown for 18.5 kW at 600V

Input Rating18.5 kW (600V Three-Phase AC (Canada / Heavy))
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)20.94 Amps
Amperage at 1.00 Power Factor (Resistive Load)17.8 Amps
Real Power (kW / Watts)18.5 kW (18,500 W)
Apparent Power (kVA) & Reactive Power (kVAR)21.76 kVA / 11.47 kVAR
Equivalent Mechanical Horsepower (HP)24.81 HP
NEC 125% Continuous Circuit Breaker30 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)10 AWG (NEC) / 2.5 mm² (IEC)

Frequently Asked Questions

How many amps is 18.5 kW at 600V (3-Phase)?

At 600V Three-Phase AC (Canada / Heavy), 18.5 kW equals 20.94 Amps at an industrial power factor of 0.85 (or 17.8 Amps at unity power factor 1.0).

What size breaker and wire is needed for 18.5 kW at 600V?

For 20.94A continuous load, NEC requires a 125% rated breaker of 30A with 10 AWG copper conductors, while IEC standard sizing uses a 25A breaker with 2.5 mm² copper cable.