20 kW to Amps at 230V Three-Phase AC

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 20 kW on a 230V Three-Phase AC circuit.

Line Current (0.85 PF)59.06 AAt 1.0 PF: 50.2 A
Active / Apparent Power20.0 kW23.53 kVA · 12.39 kVAR
Recommended Breaker80 A (NEC)60 A (IEC Nominal)
Recommended Copper Wire6 AWGIEC Metric: 16 mm²

Engineering Breakdown for 20 kW at 230V

Input Rating20 kW (230V Three-Phase AC)
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)59.06 Amps
Amperage at 1.00 Power Factor (Resistive Load)50.2 Amps
Real Power (kW / Watts)20.0 kW (20,000 W)
Apparent Power (kVA) & Reactive Power (kVAR)23.53 kVA / 12.39 kVAR
Equivalent Mechanical Horsepower (HP)26.82 HP
NEC 125% Continuous Circuit Breaker80 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)6 AWG (NEC) / 16 mm² (IEC)

Frequently Asked Questions

How many amps is 20 kW at 230V (3-Phase)?

At 230V Three-Phase AC, 20 kW equals 59.06 Amps at an industrial power factor of 0.85 (or 50.2 Amps at unity power factor 1.0).

What size breaker and wire is needed for 20 kW at 230V?

For 59.06A continuous load, NEC requires a 125% rated breaker of 80A with 6 AWG copper conductors, while IEC standard sizing uses a 60A breaker with 16 mm² copper cable.