20 kW to Amps at 415V Three-Phase AC (UK / AU)

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 20 kW on a 415V Three-Phase AC (UK / AU) circuit.

Line Current (0.85 PF)32.73 AAt 1.0 PF: 27.82 A
Active / Apparent Power20.0 kW23.53 kVA · 12.39 kVAR
Recommended Breaker45 A (NEC)35 A (IEC Nominal)
Recommended Copper Wire8 AWGIEC Metric: 6 mm²

Engineering Breakdown for 20 kW at 415V

Input Rating20 kW (415V Three-Phase AC (UK / AU))
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)32.73 Amps
Amperage at 1.00 Power Factor (Resistive Load)27.82 Amps
Real Power (kW / Watts)20.0 kW (20,000 W)
Apparent Power (kVA) & Reactive Power (kVAR)23.53 kVA / 12.39 kVAR
Equivalent Mechanical Horsepower (HP)26.82 HP
NEC 125% Continuous Circuit Breaker45 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)8 AWG (NEC) / 6 mm² (IEC)

Frequently Asked Questions

How many amps is 20 kW at 415V (3-Phase)?

At 415V Three-Phase AC (UK / AU), 20 kW equals 32.73 Amps at an industrial power factor of 0.85 (or 27.82 Amps at unity power factor 1.0).

What size breaker and wire is needed for 20 kW at 415V?

For 32.73A continuous load, NEC requires a 125% rated breaker of 45A with 8 AWG copper conductors, while IEC standard sizing uses a 35A breaker with 6 mm² copper cable.