208 kW to Amps at 600V Three-Phase AC (Canada / Heavy)
Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 208 kW on a 600V Three-Phase AC (Canada / Heavy) circuit.
Line Current (0.85 PF)235.47 AAt 1.0 PF: 200.15 A
Active / Apparent Power208.0 kW244.71 kVA · 128.91 kVAR
Recommended Breaker300 A (NEC)250 A (IEC Nominal)
Recommended Copper Wire250 kcmilIEC Metric: 120 mm²
Engineering Breakdown for 208 kW at 600V
| Input Rating | 208 kW (600V Three-Phase AC (Canada / Heavy)) |
| Amperage at 0.85 Power Factor (Industrial Motor/Transformer) | 235.47 Amps |
| Amperage at 1.00 Power Factor (Resistive Load) | 200.15 Amps |
| Real Power (kW / Watts) | 208.0 kW (208,000 W) |
| Apparent Power (kVA) & Reactive Power (kVAR) | 244.71 kVA / 128.91 kVAR |
| Equivalent Mechanical Horsepower (HP) | 278.93 HP |
| NEC 125% Continuous Circuit Breaker | 300 A |
| Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop) | 250 kcmil (NEC) / 120 mm² (IEC) |
Frequently Asked Questions
How many amps is 208 kW at 600V (3-Phase)?
At 600V Three-Phase AC (Canada / Heavy), 208 kW equals 235.47 Amps at an industrial power factor of 0.85 (or 200.15 Amps at unity power factor 1.0).
What size breaker and wire is needed for 208 kW at 600V?
For 235.47A continuous load, NEC requires a 125% rated breaker of 300A with 250 kcmil copper conductors, while IEC standard sizing uses a 250A breaker with 120 mm² copper cable.
Other Power Ratings & Voltages
5 kW at 600V (3P)10 kW at 600V (3P)15 kW at 600V (3P)20 kW at 600V (3P)25 kW at 600V (3P)30 kW at 600V (3P)45 kW at 600V (3P)50 kW at 600V (3P)75 kW at 600V (3P)100 kW at 600V (3P)150 kW at 600V (3P)200 kW at 600V (3P)250 kW at 600V (3P)500 kW at 600V (3P)208 kW at 120V Single-Phase AC208 kW at 208V Single-Phase AC208 kW at 230V Single-Phase AC (IEC)208 kW at 240V Single-Phase AC (NEC)208 kW at 208V Three-Phase AC208 kW at 230V Three-Phase AC208 kW at 400V Three-Phase AC (IEC Europe)208 kW at 415V Three-Phase AC (UK / AU)208 kW at 480V Three-Phase AC (US Industrial)208 kW at 24V DC Direct Current208 kW at 48V DC Battery / Telecom Bus