25 kW to Amps at 240V Single-Phase AC (NEC)

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 25 kW on a 240V Single-Phase AC (NEC) circuit.

Line Current (0.85 PF)122.55 AAt 1.0 PF: 104.17 A
Active / Apparent Power25.0 kW29.41 kVA · 15.49 kVAR
Recommended Breaker160 A (NEC)125 A (IEC Nominal)
Recommended Copper Wire1 AWGIEC Metric: 35 mm²

Engineering Breakdown for 25 kW at 240V

Input Rating25 kW (240V Single-Phase AC (NEC))
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)122.55 Amps
Amperage at 1.00 Power Factor (Resistive Load)104.17 Amps
Real Power (kW / Watts)25.0 kW (25,000 W)
Apparent Power (kVA) & Reactive Power (kVAR)29.41 kVA / 15.49 kVAR
Equivalent Mechanical Horsepower (HP)33.53 HP
NEC 125% Continuous Circuit Breaker160 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)1 AWG (NEC) / 35 mm² (IEC)

Frequently Asked Questions

How many amps is 25 kW at 240V (1-Phase)?

At 240V Single-Phase AC (NEC), 25 kW equals 122.55 Amps at an industrial power factor of 0.85 (or 104.17 Amps at unity power factor 1.0).

What size breaker and wire is needed for 25 kW at 240V?

For 122.55A continuous load, NEC requires a 125% rated breaker of 160A with 1 AWG copper conductors, while IEC standard sizing uses a 125A breaker with 35 mm² copper cable.