360 kW to Amps at 600V Three-Phase AC (Canada / Heavy)

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 360 kW on a 600V Three-Phase AC (Canada / Heavy) circuit.

Line Current (0.85 PF)407.54 AAt 1.0 PF: 346.41 A
Active / Apparent Power360.0 kW423.53 kVA · 223.11 kVAR
Recommended Breaker600 A (NEC)450 A (IEC Nominal)
Recommended Copper Wire600 kcmilIEC Metric: 240 mm²

Engineering Breakdown for 360 kW at 600V

Input Rating360 kW (600V Three-Phase AC (Canada / Heavy))
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)407.54 Amps
Amperage at 1.00 Power Factor (Resistive Load)346.41 Amps
Real Power (kW / Watts)360.0 kW (360,000 W)
Apparent Power (kVA) & Reactive Power (kVAR)423.53 kVA / 223.11 kVAR
Equivalent Mechanical Horsepower (HP)482.77 HP
NEC 125% Continuous Circuit Breaker600 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)600 kcmil (NEC) / 240 mm² (IEC)

Frequently Asked Questions

How many amps is 360 kW at 600V (3-Phase)?

At 600V Three-Phase AC (Canada / Heavy), 360 kW equals 407.54 Amps at an industrial power factor of 0.85 (or 346.41 Amps at unity power factor 1.0).

What size breaker and wire is needed for 360 kW at 600V?

For 407.54A continuous load, NEC requires a 125% rated breaker of 600A with 600 kcmil copper conductors, while IEC standard sizing uses a 450A breaker with 240 mm² copper cable.