38 kW to Amps at 400V Three-Phase AC (IEC Europe)

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 38 kW on a 400V Three-Phase AC (IEC Europe) circuit.

Line Current (0.85 PF)64.53 AAt 1.0 PF: 54.85 A
Active / Apparent Power38.0 kW44.71 kVA · 23.55 kVAR
Recommended Breaker90 A (NEC)70 A (IEC Nominal)
Recommended Copper Wire6 AWGIEC Metric: 16 mm²

Engineering Breakdown for 38 kW at 400V

Input Rating38 kW (400V Three-Phase AC (IEC Europe))
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)64.53 Amps
Amperage at 1.00 Power Factor (Resistive Load)54.85 Amps
Real Power (kW / Watts)38.0 kW (38,000 W)
Apparent Power (kVA) & Reactive Power (kVAR)44.71 kVA / 23.55 kVAR
Equivalent Mechanical Horsepower (HP)50.96 HP
NEC 125% Continuous Circuit Breaker90 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)6 AWG (NEC) / 16 mm² (IEC)

Frequently Asked Questions

How many amps is 38 kW at 400V (3-Phase)?

At 400V Three-Phase AC (IEC Europe), 38 kW equals 64.53 Amps at an industrial power factor of 0.85 (or 54.85 Amps at unity power factor 1.0).

What size breaker and wire is needed for 38 kW at 400V?

For 64.53A continuous load, NEC requires a 125% rated breaker of 90A with 6 AWG copper conductors, while IEC standard sizing uses a 70A breaker with 16 mm² copper cable.