38 kW to Amps at 230V Three-Phase AC

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 38 kW on a 230V Three-Phase AC circuit.

Line Current (0.85 PF)112.22 AAt 1.0 PF: 95.39 A
Active / Apparent Power38.0 kW44.71 kVA · 23.55 kVAR
Recommended Breaker150 A (NEC)125 A (IEC Nominal)
Recommended Copper Wire2 AWGIEC Metric: 35 mm²

Engineering Breakdown for 38 kW at 230V

Input Rating38 kW (230V Three-Phase AC)
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)112.22 Amps
Amperage at 1.00 Power Factor (Resistive Load)95.39 Amps
Real Power (kW / Watts)38.0 kW (38,000 W)
Apparent Power (kVA) & Reactive Power (kVAR)44.71 kVA / 23.55 kVAR
Equivalent Mechanical Horsepower (HP)50.96 HP
NEC 125% Continuous Circuit Breaker150 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)2 AWG (NEC) / 35 mm² (IEC)

Frequently Asked Questions

How many amps is 38 kW at 230V (3-Phase)?

At 230V Three-Phase AC, 38 kW equals 112.22 Amps at an industrial power factor of 0.85 (or 95.39 Amps at unity power factor 1.0).

What size breaker and wire is needed for 38 kW at 230V?

For 112.22A continuous load, NEC requires a 125% rated breaker of 150A with 2 AWG copper conductors, while IEC standard sizing uses a 125A breaker with 35 mm² copper cable.