4 kW to Amps at 400V Three-Phase AC (IEC Europe)

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 4 kW on a 400V Three-Phase AC (IEC Europe) circuit.

Line Current (0.85 PF)6.79 AAt 1.0 PF: 5.77 A
Active / Apparent Power4.0 kW4.71 kVA · 2.48 kVAR
Recommended Breaker10 A (NEC)10 A (IEC Nominal)
Recommended Copper Wire14 AWGIEC Metric: 1.5 mm²

Engineering Breakdown for 4 kW at 400V

Input Rating4 kW (400V Three-Phase AC (IEC Europe))
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)6.79 Amps
Amperage at 1.00 Power Factor (Resistive Load)5.77 Amps
Real Power (kW / Watts)4.0 kW (4,000 W)
Apparent Power (kVA) & Reactive Power (kVAR)4.71 kVA / 2.48 kVAR
Equivalent Mechanical Horsepower (HP)5.36 HP
NEC 125% Continuous Circuit Breaker10 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)14 AWG (NEC) / 1.5 mm² (IEC)

Frequently Asked Questions

How many amps is 4 kW at 400V (3-Phase)?

At 400V Three-Phase AC (IEC Europe), 4 kW equals 6.79 Amps at an industrial power factor of 0.85 (or 5.77 Amps at unity power factor 1.0).

What size breaker and wire is needed for 4 kW at 400V?

For 6.79A continuous load, NEC requires a 125% rated breaker of 10A with 14 AWG copper conductors, while IEC standard sizing uses a 10A breaker with 1.5 mm² copper cable.