4 kW to Amps at 240V Single-Phase AC (NEC)

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 4 kW on a 240V Single-Phase AC (NEC) circuit.

Line Current (0.85 PF)19.61 AAt 1.0 PF: 16.67 A
Active / Apparent Power4.0 kW4.71 kVA · 2.48 kVAR
Recommended Breaker25 A (NEC)20 A (IEC Nominal)
Recommended Copper Wire10 AWGIEC Metric: 4 mm²

Engineering Breakdown for 4 kW at 240V

Input Rating4 kW (240V Single-Phase AC (NEC))
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)19.61 Amps
Amperage at 1.00 Power Factor (Resistive Load)16.67 Amps
Real Power (kW / Watts)4.0 kW (4,000 W)
Apparent Power (kVA) & Reactive Power (kVAR)4.71 kVA / 2.48 kVAR
Equivalent Mechanical Horsepower (HP)5.36 HP
NEC 125% Continuous Circuit Breaker25 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)10 AWG (NEC) / 4 mm² (IEC)

Frequently Asked Questions

How many amps is 4 kW at 240V (1-Phase)?

At 240V Single-Phase AC (NEC), 4 kW equals 19.61 Amps at an industrial power factor of 0.85 (or 16.67 Amps at unity power factor 1.0).

What size breaker and wire is needed for 4 kW at 240V?

For 19.61A continuous load, NEC requires a 125% rated breaker of 25A with 10 AWG copper conductors, while IEC standard sizing uses a 20A breaker with 4 mm² copper cable.