46 kW to Amps at 230V Single-Phase AC (IEC)

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 46 kW on a 230V Single-Phase AC (IEC) circuit.

Line Current (0.85 PF)235.29 AAt 1.0 PF: 200.0 A
Active / Apparent Power46.0 kW54.12 kVA · 28.51 kVAR
Recommended Breaker300 A (NEC)250 A (IEC Nominal)
Recommended Copper Wire250 kcmilIEC Metric: 120 mm²

Engineering Breakdown for 46 kW at 230V

Input Rating46 kW (230V Single-Phase AC (IEC))
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)235.29 Amps
Amperage at 1.00 Power Factor (Resistive Load)200.0 Amps
Real Power (kW / Watts)46.0 kW (46,000 W)
Apparent Power (kVA) & Reactive Power (kVAR)54.12 kVA / 28.51 kVAR
Equivalent Mechanical Horsepower (HP)61.69 HP
NEC 125% Continuous Circuit Breaker300 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)250 kcmil (NEC) / 120 mm² (IEC)

Frequently Asked Questions

How many amps is 46 kW at 230V (1-Phase)?

At 230V Single-Phase AC (IEC), 46 kW equals 235.29 Amps at an industrial power factor of 0.85 (or 200.0 Amps at unity power factor 1.0).

What size breaker and wire is needed for 46 kW at 230V?

For 235.29A continuous load, NEC requires a 125% rated breaker of 300A with 250 kcmil copper conductors, while IEC standard sizing uses a 250A breaker with 120 mm² copper cable.