⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🏭 Industrial Electrical Conversion · Three-Phase & Single-Phase

46 kW to Amps at 480V Three-Phase AC (US Industrial)

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 46 kW on a 480V Three-Phase AC (US Industrial) circuit.

Line Current (0.85 PF)65.09 AAt 1.0 PF: 55.33 A
Active / Apparent Power46.0 kW54.12 kVA · 28.51 kVAR
Recommended Breaker90 A (NEC)70 A (IEC Nominal)
Recommended Copper Wire4 AWGIEC Metric: 16 mm²

Engineering Breakdown for 46 kW at 480V

Input Rating46 kW (480V Three-Phase AC (US Industrial))
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)65.09 Amps
Amperage at 1.00 Power Factor (Resistive Load)55.33 Amps
Real Power (kW / Watts)46.0 kW (46,000 W)
Apparent Power (kVA) & Reactive Power (kVAR)54.12 kVA / 28.51 kVAR
Equivalent Mechanical Horsepower (HP)61.69 HP
NEC 125% Continuous Circuit Breaker90 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)4 AWG (NEC) / 16 mm² (IEC)

Frequently Asked Questions

How many amps is 46 kW at 480V (3-Phase)?

At 480V Three-Phase AC (US Industrial), 46 kW equals 65.09 Amps at an industrial power factor of 0.85 (or 55.33 Amps at unity power factor 1.0).

What size breaker and wire is needed for 46 kW at 480V?

For 65.09A continuous load, NEC requires a 125% rated breaker of 90A with 4 AWG copper conductors, while IEC standard sizing uses a 70A breaker with 16 mm² copper cable.