🏭 Industrial Electrical Conversion · Three-Phase & Single-Phase

58 kW to Amps at 480V Three-Phase AC (US Industrial)

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 58 kW on a 480V Three-Phase AC (US Industrial) circuit.

Line Current (0.85 PF)82.07 AAt 1.0 PF: 69.76 A
Active / Apparent Power58.0 kW68.24 kVA · 35.95 kVAR
Recommended Breaker110 A (NEC)90 A (IEC Nominal)
Recommended Copper Wire4 AWGIEC Metric: 25 mm²

Engineering Breakdown for 58 kW at 480V

Input Rating58 kW (480V Three-Phase AC (US Industrial))
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)82.07 Amps
Amperage at 1.00 Power Factor (Resistive Load)69.76 Amps
Real Power (kW / Watts)58.0 kW (58,000 W)
Apparent Power (kVA) & Reactive Power (kVAR)68.24 kVA / 35.95 kVAR
Equivalent Mechanical Horsepower (HP)77.78 HP
NEC 125% Continuous Circuit Breaker110 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)4 AWG (NEC) / 25 mm² (IEC)

Frequently Asked Questions

How many amps is 58 kW at 480V (3-Phase)?

At 480V Three-Phase AC (US Industrial), 58 kW equals 82.07 Amps at an industrial power factor of 0.85 (or 69.76 Amps at unity power factor 1.0).

What size breaker and wire is needed for 58 kW at 480V?

For 82.07A continuous load, NEC requires a 125% rated breaker of 110A with 4 AWG copper conductors, while IEC standard sizing uses a 90A breaker with 25 mm² copper cable.